[6-3 Evaluating and Adjusting Refrigerant Charge ]
6-3-3

Maximum refrigerant charge

There is a limit to the amount of refrigerant that can be charged into a unit. Observe the maximum refrigerant charge in the
table below.
HP72-240T(Y)(S)NU-A
Total index of the outdoor units
Factory charge (kg)
Factory charge (lbs - oz)
Maximum additional refrigerant
charge on site (kg)
Maximum additional refrigerant
charge on site (lbs - oz)
Maximum refrigerant charge (kg)
Maximum refrigerant charge (lbs - oz)
HWE18240_GB
HP72
HP96
HP120
9.8
10.8
10.8
21 - 10
23 - 13
23 - 13
19.9
22.5
23.9
43 - 14
49 - 10
52 - 12
29.7
33.3
34.7
65 - 8
73 - 7
76 - 8
HP144
HP192
HP240
19.6
21.6
21.6
43 - 4
47 - 10
47 - 10
31.3
31.1
32.0
69 - 1
68 - 10
70 - 9
50.9
52.7
53.6
112 - 4
116 - 3
118 - 3
3
chapter 6 -