Procedure for extracting the machine from the container.
Container Kit Optional

Figure 3 - Lifting the unit

The number and the location of lifting points changes from model to model. This picture is for reference only. Lifting tools
(bars, ropes, etc) are not supplied.
Both the lifting ropes and the spacing bar and/or scales must be strong enough to support the machine safely. Please
check the unit's weight on the machine's nameplate.
The weights shown in the "Technical specifications" tables in the "Specifications" chapter refer to standard units.
Specific units might have accessories that increase overall weight (pumps, heat recovery, copper condenser coils, etc.).
The unit must be lifted with the utmost attention and care. Avoid jolting when lifting and lift unit very slowly, keeping it
perfectly orizzontal.

Positioning and assembly

All units are designed for installation outdoors, either on roofs or on the ground, provided that the installation area is free
of obstacles that could reduce air flow to the condensers bank.
The unit must be installed on a robust and perfectly plan foundation; should the machine be installed on balconies or
roofs, it might be necessary to use weight distribution beams.
For installation on the ground, a strong cement base that is at least 250 mm wider and longer than the machine must be
provided. Also, this base must be able to support the weight of the machine as stated in the technical specifications.
If the machine is installed in places that are easily accessible to people and animals, it is advisable to install protection
grids for the condenser and compressor sections.
To ensure the best possible performance on the installation site, the following precautions and instructions must be
followed:
Avoid air flow recirculation.
Make sure that there are no obstacles to hamper air flow.
Air must circulate freely to ensure proper flow in and flow out.
Make sure to provide a strong and solid foundation to reduce noise and vibrations as much as possible.
Avoid installation in particularly dusty environments, in order to reduce soiling of condensers.
The water in the system must be particularly clean and all traces of oil and rust must be removed. A mechanical
water filter must be installed on the machine's inlet piping.