Procedure
Procedure
Building Technologies
HVAC Products
3.3.4 Setting up the DOE4IN Batibus input
modules
1.
Check wiring with the help of the supplier's Data Sheet.
2.
Apply power.
3.
Select the address by turning the address knob:
The segment number with the knob at the top
(recommendation: Segment 4)
The device number with the knob at the bottom
(recommendation: 1, 5, 9 and 13)
4.
Connect the module to the LPB.
5.
Check the connection:
In normal operation, the orange LED flashes.
3.3.5
Setting up the DOE4RE Batibus relay
modules
1.
Check wiring with the help of the supplier's Data Sheet.
2.
Apply power.
3.
Using a screwdriver, set all outputs to "Auto".
4.
Select the address by turning the address knob:
The segment number with the knob at the top
(recommendation: Segment 4)
The device number with the knob at the bottom
(recommendation: 1, 5, 9 and 13)
5.
Connect the module to the LPB.
6.
Check the connection:
In normal operation, the orange LED flashes.
User Manual OCI600
Local setting up
31/72
74 319 0002 0 c
15.07.2005