Setting Up The Aew2.1 Pulse Adapter - Siemens OCI600 User Manual

Central communication unit
Table of Contents

Advertisement

Note
Note
Addressing
Building Technologies
HVAC Products
In the case of large plant with the central bus power sup-
ply and controller bus power supply on at the same time,
an overcurrent on the bus can occur. For damage result-
ing from this kind of situation, Siemens will not assume
any responsibility.
6.
Set the parameters of the controller (refer to Installation
Instructions of the relevant device).
7.
Connect the controller to the bus via the LPB connector.
3.3.2

Setting up the AEW2.1 pulse adapter

The pulse adapter must be set up with the help of the
AZW30 service unit. For detailed information about the
AZW30, refer to SYNERGYR User Manual U2841.
For setting up the pulse adapter, a PTG1... address plug is
required.
Permissible addresses if ...
1 OCI600 is con-
nected to the bus
1, 3, 5, 7, 9, 11
1)
(PTG1.16)
1)
On the OCI600, a maximum of 6 pulse adapters with 2 inputs can be
parameterized
2)
With the OCI600, 3 pulse adapters with 2 inputs or 6 pulse adapters with 1
input can be used
When using addresses 124, 125 and 126, it is only inputs
"Counter 1 (P1–M)" of the pulse adapters that may be used.
User Manual OCI600
Local setting up
1 OCI600 and 1 OZW30 are
connected to the bus
121...126
2)
(PTG1.128)
27/72
74 319 0002 0 c
15.07.2005