Installation - YASKAWA VS-616PC5 Series Option Instruction Manual

Isolated 4-20ma output monitor card cm-b2/p
Table of Contents

Advertisement

INSTALLATION

1. Before attempting to install or use the Isolated Monitor Card CM-B2/P, read these instructions.
2. After unpacking the card, verify that you have received the correct code number and that no dam-
age has occurred during shipping. Contact your YASKAWA representative if you should require
any assistance.
3. Turn OFF the main electrical power to the inverter.
4. Remove the inverter's cover by first removing the digital operator. Then push inward (on the
cover) at the indented area located on each side of the cover, and lift the cover upward from the
rear of the cover. Refer to the VS-616PC5/P5 User's Manual (YEA-TOA-S616-12), if necessary.
5. Check that the indicator CHARGE LED is OFF (indication that power is OFF).
6. Place the Isolated Monitor Card onto the four (4) stand-off posts in the control board aligning the
Isolated Monitor Card's connector with the control board's 2CN connector.
7. Gently push the Isolated Monitor Card downward onto the stand-off posts until they protrude
through the card's holes, thereby engaging the card firmly to the posts.
8. Plug the Isolated Monitor Card's connector into the Control Board's 2CN connector.
9. Replace the inverter's cover. Refer to Fig. 1 for correct wiring of the Isolated Monitor Card and
the Control Board.
Page 4
VS-616PC5/P5 Option Instruction Manual: Isolated Monitor Card CM-B2/P

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vs-616p5 series

Table of Contents