[5-1 Dipswitch Functions and Factory Settings ]
5-1-3
Function of the Switch <Remote Controller>
(1) MA remote controller (PAR-20MAA)
The SW is located at the bottom of the remote controller under the cover. Operate the switches to perform the remote con-
troller main/sub setting or other function settings. Normally, do not change the settings of switches other than the SW1 (main/
sub switching switch). (All the switches are set to "ON" at factory setting.)
ON
1
2
3
4
5
6
7
8
9 10
Switch
Function
Remote controller
1
main/sub setting
At power on of the
2
remote controller
-
3
Suction temperature display
4
(discharge temperature display)
8
- chapter 5
ON
1
2
3
4
Switching switch
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
ON
OFF
Main
Normal
Timer mode
startup
startup
-
Displayed
Not displayed
Remote controller
Operation by switch settings
When two remote controllers are connected
Sub
to one group, set either of the remote
controllers to "Sub".
To resume the operation with timer mode
after the power is restored when the
schedule timer is connected, set to
"Timer mode startup".
-
-
When the suction temperature (discharge
temperature) display is not necessary,
set to "Not displayed".
Switch setting timing
Before power on
Before power on
-
Before power on
BS_05_C