[2-7 Example System with an MA Remote Controller ]
(4) Wiring method
1) Indoor/outdoor transmission line
Connect M1, M2 terminals of the indoor/outdoor trans-
mission line terminal block (TB3) on the outdoor unit (OC
and OS) and A1, B1 terminals of the indoor/outdoor ter-
minal block (TB5-1) on the indoor unit (IC). (Non-polar-
ized 2-core cable)
Only use shielded cables.
(5) Address setting method
Procedures
Unit or controller
1
Indoor
unit
2
Outdoor unit
3
MA
remote
controller
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
Units are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the
same).
12
- chapter 2
Address
setting range
Main unit
IC
01 to 50
Sub unit
IC
01 to 50
OC
51 to 100
OS
Main
MA
No settings
remote
required.
controller
Sub
MA
Sub
remote
remote
controller
controller
Shielded cable connection
Connect the earth terminal of the OC and S terminal of
the IC terminal block (TB5-1).
2) Switch setting
Address setting is required as follows.
Setting method
Assign a sequential odd number
starting with "01" to the upper in-
door controller.
Assign sequential numbers start-
ing with the address of the main
unit in the same group. (Main
unit address +1)
Assign sequential numbers to
the outdoor units starting with the
number that equals the address
of the indoor unit in the same re-
frigerant circuit plus 50.
-
Settings to be made with the sub/
main switch
Factory
Notes
setting
00
00
Main
BS_02_C