Mitsubishi Electric PUHY-P250YNW-A Service Handbook page 45

Hide thumbs Also See for PUHY-P250YNW-A:
Table of Contents

Advertisement

[2-7 Example System with an MA Remote Controller ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as 2-7-1
2) MA remote controller wiring
Group operation of indoor units
To perform a group operation of indoor units (IC), daisy-
chain terminals 1 and 2 on the terminal block (TB15) on
all indoor units (IC). (Non-polarized 2-core cable)
(5) Address setting method
Procedures
1
Indoor
unit
2
Outdoor unit
3
MA
remote
controller
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
Units are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the
same).
18
- chapter 2
Unit or controller
setting range
Main unit
IC
01 to 50
Sub unit
IC
01 to 50
OC
51 to 100
OS
Main
MA
No settings
remote
required.
controller
Sub
MA
Sub
remote
remote
controller
controller
Set the Main/Sub switch on one of the MA remote con-
trollers to SUB.
3) Switch setting
Address setting is required as follows.
Address
Setting method
Assign a sequential odd number
starting with "01" to the upper in-
door controller.
Assign sequential numbers start-
ing with the address of the main
unit in the same group. (Main
unit address +1)
Assign sequential numbers to
the outdoor units starting with the
number that equals the address
of the indoor unit in the same re-
frigerant circuit plus 50.
Settings to be made with the sub
/ main switch
Notes
-
Factory
setting
00
00
Main
BS_02_C

Advertisement

Table of Contents
loading

This manual is also suitable for:

Puhy-p500ysnw-aPfd-p250vm-ePfd-p500vm-e

Table of Contents