[3-4 Functions of the Major Components of Outdoor Unit ]
Part
Symbols
name
(functions)
Sole-
SV1a
noid
Discharge-
valve
suction
bypass
SV2
SV9
SV10
SV11
Linear
LEV1
expan-
(SC control)
sion
valve
LEV9
(Refrigerant
flow adjust-
ment)
LEV2a
(Refrigerant
flow adjust-
ment)
LEV2b
(Refrigerant
flow adjust-
ment)
4-way
21S4a
valve
21S4b
Fan
FAN motor 1
motor
14
- chapter 3
Notes
Usage
1) High/low pressure bypass at
start-up and stopping, and
capacity control during low-
load operation
2) High-pressure-rise preven-
tion
Makes excessive refrigerant in the
accumulator evaporate
High-pressure-rise prevention
-
-
Adjusts the amount of bypass flow
from the liquid pipe on the outdoor
unit during cooling
Adjusts the flow of refrigerant by-
passed from the pipe for cooling
the control board when the control
board temperature rises
-
Control refrigerant distribution
(OC and OS)
Control refrigerant distribution
(OC and OS)
Heat exchanger capacity control
Regulates the heat exchanger ca-
pacity by adjusting the operating
frequency and operating the pro-
peller fan based on the operating
pressure.
Specifications
AC220-240V
Open while being powered/
closed while not being pow-
ered
Open while being powered/
closed while not being pow-
ered
Open while being powered/
closed while not being pow-
ered
Open while being powered/
closed while not being pow-
ered
Open while being powered/
closed while not being pow-
ered
DC12V
Opening of a valve driven by a
stepping motor 0-480 pulses
DC12V
Opening of a valve driven by a
stepping motor 2100 pulses
(Max. 3000 pulses)
AC220-240V
AC220-240V
AC380-400V, 920W
Check method
Continuity check
with a tester
Same as indoor
LEV
The resistance val-
ue differs from that
of the indoor LEV.
Refer to the follow-
ing page(s). [8-8
Troubleshooting
LEV Problems]
Continuity check
with a tester
Continuity between
white and orange.
Continuity between
yellow, red, and
blue.
White
M
Orange
Yellow
red Blue
Continuity check
with a tester