Table 19. Expanded operating temperature specifications (continued)
Expanded operating temperature
< 1% of annual operating hours
NOTE:
When operating in the expanded temperature range, system performance may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD
panel and in the System Event Log.

Expanded operating temperature restrictions

Do not perform a cold startup below 5°C.
135 W (4 core, 6 core, or 8 core) and 145 W processors are not supported.
Non-Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
PCIeSSD is not supported.
When populating the server module slots in the PowerEdge VRTX enclosure with only PowerEdge M630 server modules:
○ Install 86 mm width heat sink for processors of 120 W or more
○ Install 68 mm width heat sink for processors of less than 120 W.
○ If you install a blade with two processors in the M1000e enclosure, all blade slots in the enclosure must have PowerEdge M630
blades with the same configuration (PowerEdge M630 blades with two processors). However, vacant blade slots in the enclosure
can be installed with blade blanks.
20
Technical specifications
Specifications
For temperatures between 35°C and 40°C, derate maximum
allowable temperature by 1°C per 175 m above 950 m (1°F per 319
ft).
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature
(10°C to 35°C), the system can operate down to –5°C
or up to 45°C for a maximum of 1% of its annual
operating hours.
For temperatures between 40°C and 45°C, de-rate maximum
allowable temperature by 1°C per 125 m above 950 m (1°F per 228
ft).