Connecting

5.1

Wiring rules

L1(L), L2(N), L3, PE
1.
SZF 1-0.6-3.5
2.
AWG
Line protection
The line protection of the SIMATIC ET 200SP motor starter is provided for the motor
outgoing feeder cable when the following condition is met:
The cross-section of the motor outgoing feeder cable must be dimensioned for the load
ratios of the motor and for the cable-laying method.
Comply with national regulations, e.g. DIN VDE 0298-4.
The conductor protection for the incoming feeders must be ensured by the owner of the
installation depending on the cross-section.
Motor starter
System Manual, 04/2016, A5E35582704002A/RS-AA/001
1x 1 ... 6 mm²
1x 1 ... 6 mm²
1x 1 ... 6 mm²
1x 1 ... 4 mm²
1x 18...10
WARNING
T1, T2, T3, PE, 24 V DC, M
1x 0.5 ...
2.5 mm²
1x 0.5 ...
2.5 mm²
1x 0.5 ...
2.5 mm²
1x 0.5 ...
1.5 mm²
AWG
1x 20...12
5
DI1 ... DI3, LC, M, 24 V OUT
1x 0.2
...1.5 mm²
1x 0.2
...1.5 mm²
1x 0.25
...1.5 mm²
1x 0.25 ...
0.75 mm²
AWG
1x 24 ... 16