TROUBLESHOOTING

8.3.2 MELSECNET/H error code list

Error code
(Error detected by the programmable
4000 to 4FFF
controller CPU)
(Error detected by the serial
7000 to 7FFF
communication module, etc.)
B000 to BFFF (Error detected by the CC-Link module)
C000 to CFFF (Error detected by the Ethernet module)
(Error detected by CC-Link IE Field
D000 to DFFF
Network)
(Error detected by CC-Link IE Controller
E000 to EFFF
Network)
F101
Initial status (Network activated)
F102
Initial status (Network activated)
F103
Initial status (during online test)
Initial status
F104
(Control/sub-control station shift)
F105
Initial status (Parameters being processed)
Shift from failed control station to sub-
F106
control station
F107
Baton pass error (baton lost)
F108
Baton pass error (duplicate baton)
F109
Initial status (during online test)
F10A
Initial status (online test/offline loop test)
F10B
Duplicate station number error
F10C
Duplicate control station error
F10D
Offline status
F10E
Number of receive error retries exceeded
F10F
Number of send error retries exceeded
F110
Timeout error
8 - 35
Table 8.1 Error code list
Description
Take measures referring to the QCPU User's Manual (Hardware Design,
Maintenance and Inspection).
Take measures referring to the troubleshooting section of the Serial
Communication Module User's Manual.
Take measures referring to the troubleshooting section of the CC-Link System
Master/Local Module User's Manual.
Take measures referring to the troubleshooting section of the Ethernet Interface
Module User's Manual.
Take measures referring to the troubleshooting section of the CC-Link IE Field
Network User's Manual.
Take measures referring to the troubleshooting section of the CC-Link IE
Controller Network Reference Manual.
Wait until SB0047 (baton pass status) and SB0049 (data link status) turn off
(normal).
Check the condition of the control station's power supply and of the cables and
the status of the control station CPU module.
Check the line status for a faulty cable or a missing terminating resistor, as well
as the stations that are not powered on.
In the case of the PLC to PLC network, when transient transmission is
executed frequently and the link scan time may exceed 200 ms, adjust the
transient setting values to reduce the link scan time.
Execute a setup confirmation test to check whether the same station number
has been set for two or more stations or whether two or more control stations
exist.
Check for faulty cables, wire breakage, poor connector connections, connection
errors, uninstalled or loose terminating resistors, etc.
Wait until SB0047 (baton pass status) and SB0049 (data link status) are
recovered.
<During execution of an online test>
Wait until SB0047 (baton pass status) and SB0049 (data link status) are
recovered.
<During execution of an offline test>
Change the switch setting to online after the test has been completed.
Review the station number setting.
The setup confirmation test of network diagnosis is effective.
Review the station number setting.
The setup confirmation test of network diagnosis is effective.
Review the mode setting, and change it to online.
Check for faulty cables, faulty hardware, incorrect cable wiring, and absence of
terminating resistor (in the case of the bus). In addition, check whether the
same station number has been set for two or more stations or whether two or
more control stations or remote master stations exist.
The setup confirmation test and loop test of network diagnosis are effective.
MELSEC-Q
Corrective action
8 - 35