Measuring The Backup Time; How To Measure Backup Time - Omron BU5002R Instruction Manual

Ups/200 to 240 v
Table of Contents

Advertisement

4 Maintenance and inspection

4-3 Measuring the backup time

■ Battery inspection (measurement of backup time) guidelines and frequency
Ambient temperature
* The battery deteriorates even if it is stored. The higher the temperature is, the shorter the
life becomes.
4-3 Measuring the backup time

4-3-1 How to measure backup time

The backup time you measure for the first time after purchase is the "initial value of the
backup time". Thereafter when battery inspection is performed, the battery degradation
status can be more accurately judged when the "initial value of backup time" has been
measured.
(1) Connect to commercial power and charge the battery for 8 hours or more.
(2) Turn ON all devices connected to the unit.
(3) Turn off the commercial power and measure the backup time.
In Battery Mode, measure the time until the unit automatically stops and all displays
disappear.
96
Every 6-months check
40°C
For 1 year after purchase
30°C
For 3 years after purchase
25°C
For 4 years after purchase
The power supply output of the unit will stop when the battery discharges.
Conduct measurement under a condition in which no problem occurs even if the
power supply of the connected device stops during the process. Do not conduct
measurement if there is a possibility of a failure when the power supply stops.
Every time an expansion battery unit is connected, the charging time is increased by
16 hours for each unit.
Monthly check
1 year or more after
commencement of use
3 years or more after
commencement of use
4 years or more after
commencement of use
BU5002R/BU3002R/BU3002RH