Commissioning Guidelines
1st step: Install ASM in STEP 7
S ASM 475, 473: The installation program for the ASM 475, 473 must be
executed once on the STEP 7 PC.
S PROFIBUS-ASM: The device master file (Siem80B6.GSD for ASM 452)
must be linked to the device catalog with HW Config (Extras/Neue GSD
installieren ...).
2nd step: Configure hardware in STEP 7
The configuration varies depending on which MOBY ASM is being used.
S ASM 475: Central setup on S7-300
S ASM 475, 473: Distributed setup with PROFIBUS and ET 200M, ET 200X
S ASM 452: Distributed setup with PROFIBUS
The following figure shows the placement of the MOBY ASMs in the hardware
catalog.
ASM 475 in
central setup
Figure 8-1 Placement of the MOBY ASMs in the hardware catalog
When placing the ASMs, make sure that the I address and the Q address have the
same values. The value in the "I address" field must be used later in the STEP 7
project as the ASM_address variable. If a MOBY ASM has more than one channel
(e.g., ASM 475 = 2 channels), the same I address must be used for every channel.
The following figure shows an example of a hardware: configuration.
FC 56
J31069-D0155-U001-A0-7618
Example: ASM 475 in
distributed setup with
ET 200M
8
ASM 452 in distributed
setup with PROFIBUS
8-1