Hoshizaki KM-150BAF Service Manual page 20

Crescent cuber
Hide thumbs Also See for KM-150BAF:
Table of Contents

Advertisement

3) Drain Timer
The Drain Timer is factory-adjusted, and no adjustment is required.
SETTING
Dip Switch
No. 3
OFF
ON
OFF
ON
T1: Time to drain the Water Tank
T2: Time to restrain defrost completion
4) Freeze Timer
Adjust to proper specification, or the unit may not operate correctly.
Two new dip switches numbered 9 and 10 have been added to the improved "E" board to
better prevent possible freeze ups. These settings come factory set to the default setting
of 60 min. (OFF, OFF). Check the adjustment chart published in the Tech Specs for
proper settings. If the old board does not have these two dip switches, (only 8 instead of
10), leave setting as OFF, OFF.
Dip Switch
No. 9
OFF
ON
OFF
ON
Dip Switch
No. 4
OFF
OFF
ON
ON
CAUTION
SETTING
Dip Switch
No. 10
OFF
OFF
ON
ON
TIME
T1
10 seconds
150 seconds
10 seconds
180 seconds
10 seconds
120 seconds
20 seconds
180 seconds
TIME
60 min.
70 min.
50 min.
60 min.
20