Installer Mode - Westinghouse WBRC 140 Series Installation, Start-Up, Maintenance, Parts, Warranty

Gas fired residential floor and wall mount combi boilers
Table of Contents

Advertisement

I. Installer Mode
Installer Mode will activate when button
Figure 47 - Installer Mode Screens
Display
Default
1:EH
E0.00
2:cE
OFF
3:In
OFF
4:Fu
GA
5:St
ON
6:OH
68F
7:OL
5F
8:FH
00
9:FH
00
10:dr
NO
11:dl
NO
12:bt
0
13:Ft
1
14:bo
27F
15:OF
68F
16:cH
180F
is pressed and held for five seconds while the boiler display is powered Off.
Detail
Error history up to 10
Clear Error History
System Reset
(Factory Setting)
Water Volume Unit
Stored Water Heating Function
Maximum Outdoor
Temperature
Minimum Outdoor
Temperature
Maximum Fan Speed
Minimum Fan Speed
Reset burner operation time
Reset ignition cycle
Boost Function
CH Anti-Frequency Time
Set differential temperature to
turn burner "ON"
Warm Weather Shutdown
Maximum Supply Temperature
Check ten most recent Error Codes (E0 - E9)
Select "ON" to Clear Error History. Range: ON or OFF
Select "ON" to restore system to default factory settings
(Burner operation time, Ignition cycles, and Supply power time will not be reset. See
Functions 10 and 11.)
Range: ON or OFF
Select "OFF" to turn off this function
Range: ON or OFF
When used with an outdoor sensor, sets the maximum outdoor design temperature
for the system design. Maximum outdoor temperature must be set 9
minimum outdoor temperature.
Range: (Minimum Outdoor Temperature + 9
Sets the minimum outdoor design temperature for the system. Minimum outdoor
temperature must be set at least 9
o
Range: -4
F to (Maximum Outdoor Temperature - 9
Adjusts Maximum Fan Speed
Adjusts Minimum Fan Speed
Select YES to reset burner operation time
Range: NO or YES
Select YES to reset ignition cycles
Range: NO or YES
When Outdoor Temperature Mode is used, this function boosts CH temperature to
the maximum supply temperature based on the outdoor reset curve if set point is
not reached within the set period of time.
Range: 0 - 120 min
NOTE: "0" means Boost Function is OFF.
This function delays burner operation during CH mode.
Range: 0 - 20 min
When set, the boiler will operate to heat CH water when water temperature falls
below a differential setting.
Example: If setpoint is 180
will turn on when CH water temperature falls below 153
Warm weather shut down will shut down CH Mode if the programmed outdoor
temperature is exceeded.
Range: 50 - 110
Sets the maximum design supply temperature based on the minimum outdoor
design temperature. Maximum supply temperature must be set 9
minimum supply temperature.
Range: (Minimum Supply Temperature + 9
Description
Range: GA or Li
o
F) to 110
o
F below the maximum outdoor design
temperature.
o
F)
Range: -30 - +30
Range: -30 - +30
o
o
F and differential is 27
F, the boiler
o
Range: 9 - 27
F
o
F
o
o
F) - 180
whl-648 Rev. 001 Rel. 003 Date 10.8.19
49
o
F above the
o
F
o
F.
o
F above the
F