Outdoor Temperature Mode (Optional) - Westinghouse WBRC 140 Series Installation, Start-Up, Maintenance, Parts, Warranty

Gas fired residential floor and wall mount combi boilers
Table of Contents

Advertisement

50
Display
Default
17:cL
86F
18:dH
140F
19:cb
100
20:db
100
21:PP
40
22:Po
5
23:PF
0
24:SF
150F
25:So
20F
26:dt
2
27:PE
1
28:HA
0-2
AP:cP
5
29:AP
cP:oFF
or
OFF
cP:on
Table 28 - Installer Mode Descriptions
Turn the dial
counterclockwise and clockwise to scroll through the displayed parameters. To view parameter details, press the
button at the appropriate screen. Turn the dial
press the
button.
To leave Installer Mode, press the
J. Outdoor Temperature Mode (Optional)
NOTE: If the system requires a fixed operating temperature, the outdoor sensor is not required and should not be installed.
There is no connection required if an outdoor sensor is not used in the installation.
1. Use a minimum 22 AWG wire for runs of 100 feet or less and minimum 18 AWG wire for runs of up to 150 feet.
2. Mount the outdoor sensor on an exterior surface of the building, preferably on the north side in an area that will not be affected by direct
sunlight and will be exposed to varying weather conditions.
NOTE: For correct mounting procedures, follow instructions provided with the sensor.
NOTE: If sensor wires are located in an area with sources of potential electromagnetic interference (EMI), the sensor wires should be shielded,
or the wires routed in a grounded metal conduit. If using shielded cable, the shielding should be connected to the common ground of the
boiler.
NOTE: Outdoor Temperature Mode Icon on the display will flash if an Outdoor Sensor or 0-10 Volt is not connected to the boiler.
whl-648 Rev. 001 Rel. 003 Date 10.8.19
Detail
Minimum Supply Temperature
Maximum DHW Setpoint
Temperature
Heating capacity
DHW capacity
Internal CH Pump Post Run
Timer, T/T Calling for Heat
Internal CH Pump Overrun
Timer (On)
Internal CH Pump Overrun
Timer (Off )
Internal DHW Storage Tank
Setpoint
Internal DHW Storage Tank
Differential
Delay time when switching
from DHW Mode to CH Mode
Internal CH Pump Post-Purge
Time, T/T Satisfied
High Elevation Mode
Internal CH Pump and Internal
DHW Storage Pump Test Mode
Internal CH Pump and Internal
DHW Storage Pump Test Mode
counterclockwise and clockwise to change the selected parameter. To save the setting
button again. The display will return to power off mode.
Sets the minimum design supply temperature based on the maximum outdoor
design temperature. Minimum supply temperature must be set 9
maximum supply temperature.
o
Range: 86
F (Maximum Supply Temperature - 9
Sets Maximum DHW Setpoint Temperature
Range: 120 - 140
Sets heating combustion rate
NOTE: 199 Models shall be factory set at 70%. The default number will be 70. This
percentage can be increased with an additional pump.
Set DHW combustion rate
When boiler CH setpoint is satisfied, but T/T is calling for heat, the burner will shut
OFF and the CH pump will continue to run for this set amount of time
Range: 1 - 60 minutes
This function runs the Internal CH Pump after the Internal CH Pump Post Run Timer
has completed. This will cycle the Internal CH Pump again based on the default
programmed Off and On cycles and repeats until the central heating call is satisfied.
Range: 1 - 60 minutes
Sets the Internal DHW Storage Tank Setpoint
Range: 140 - 167
Sets the Internal DHW Storage Tank Differential
Range: 140 - 167
Range: 0 - 2 Minutes
Allows the user to set the boiler pump post purge time once the boiler CH setpoint
and thermostat are satisfied.
Range: 1-5 minutes
This boiler may be installed at elevations up to 10,000 feet and operate on either
Natural or LP. The boiler will de-rate by 4% for each 1000 feet above sea level. Select
the appropriate installation location as described below.
Selects Installation Location for Proper Boiler Operation at Altitude:
0-2 for installation locations from sea level to 1999 feet
2-5 for locations from 2000 to 4999 feet
5-8 for locations from 5000 to 7999 feet,
8-10 for locations from 8000 to 10000 feet
NOTE: Use a calibrated combustion analyzer to ensure CO and CO2 are within the
ranges shown in this manual. Adjust the offset screw in the clockwise (positive) or
counterclockwise (negative) directions (approximately 1/8 turn) if the measured CO2
value on LOW FIRE is out of range.
This function sets the time to run both the Internal CH and Internal DHW Storage
pumps to purge air from the system. Range: 1 – 30 minutes
Turn this function on to activate Internal CH and Internal DHW Storage pump
testing. Only works in Installation Mode. Turns off during normal operation.
Description
o
F)
o
F
Range: 50 - 100%
Range: 50 - 100%
o
F
o
F
Default: 0 – 2
o
F above the

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents