Agency Approvals

Both module points will be used to drive the output of the AV unit to the desired pattern below:
Base Address
OFF
ON
ON
OFF
NOTE: To configure an audible/visual unit to silence only the audible component with a signal silence command, configure both addresses
to activate for the alarm condition, the base address shall be non-silenceable and the base+1 shall be silenceable with the appropriate
resound settings.
W-SYNC - Wireless Addressable Sync Module
The wireless sync module is 24VDC externally powered and requires 4 supplemental CR123A batteries. The module has an LED to
indicate the activation and trouble status. The wireless sync module will occupy two consecutive SLC module addresses.
Base address set by the code wheels on the sync module will use:
Type Code: Wireless Relay - Output
Base+1 address will use the following configuration:
Type Code: NAC Module - Output
Wireless related trouble events described in Section 3.6.3 will be indicated at the base address.
The end of line supervision of the monitor input and the power monitoring of the external 24VDC supply will be indicated at the base+1
address.
The following table indicates the output state.
Base Address
OFF
ON
ON
OFF
NOTE:
1. To configure a NAC circuit, with audible and visual units, to silence only the audible component with a signal silence command, configure
both addresses to activate for the alarm condition. The base address shall be non-silenceable and the base+1 shall be silenceable with the
appropriate resound settings.
2. When the sync module is being used for delivering only the synchronization signal (i.e. applications with the MDL3), it is recommended to
leave the base address point constantly active to eliminate any delay in initial synchronization.
NOTE: When a wireless relay, wireless AV base, or wireless sync module is in use in the system, module device count must be limited to
109 modules per loop. This includes wired and wireless modules that are on the same loop. The module address range must be within 1-
109.
3.2 Agency Approvals
3.2.1 FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1.
This device may not cause harmful interference.
2.
This device must accept any interference received, including interference that may cause undesired operation.
WARNING: DO NOT MAKE CHANGES TO THE EQUIPMENT
!
CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE MANUFACTURER COULD VOID THE USER'S
AUTHORITY TO OPERATE THE EQUIPMENT.
3.2.2 Federal Institute of Telecommunications
This device utilizes the Honeywell915 rev A radio module and complies with IFETEL standard(s).
IFT: RCPHOSW14-1983
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:G 4/13/2020
Base+1 Address
OFF
Off
OFF
Strobe Only (Audible Silenced)
ON
Strobe & Audible active
ON
Magnet Test mode (Strobe & audible activate when magnet is placed on the unit)
FCC ID: AUBWFSSM
Base+1 Address
OFF
OFF
ON
ON
Notification Pattern
Control Output Signal
Low (inactive)
Low (inactive)
High (active)
Strobe Only (Audible Silenced)
High (active)
Strobe & Audible active
High (active)
Magnet Test mode
Synchronization Output Signal
Wireless Devices