Download Print this page

Voltage Regulation - Tripp Lite SmartOnline SU20K3/3XR5 Specifications

20kva on-line double-conversion ups, 3 phase input / output with oversize battery set
Hide thumbs Also See for SmartOnline SU20K3/3XR5:

Advertisement

Nominal Input
120V / 208V 3 phase wye
Voltage(s)
Supported
UPS input
Hardwire
connection type
UPS input
120/208V (3-Phase, 4 Wire, wye)
connection
description
BATTERY
Full load runtime
17 min. (16kw)
(minutes)
Half load runtime
42 min. (8kw)
(minutes)
Expandable battery
Supports extended runtime with optional external battery packs
runtime
External battery
SURBC2030;
pack compatibility
Expandable
Includes a battery housing with space for 3 internal
runtime description
runtime capacity is available by adding
specific recommendations
DC system voltage
240
(VDC)
Battery recharge
2 - 4 hours from 10% to 90%
rate (included
batteries)
Replacement
SURBC2030
battery cartridge
(internal UPS
battery
replacement)
Battery Access
Front panel internal battery access door
Battery
Hot-swappable, replaceable batteries
replacement
description

VOLTAGE REGULATION

Voltage regulation
Online, double-conversion power conditioning
description
Overvoltage
Maintains continuous operation without using battery power during overvoltages to 144 / 250 (3-Phase, 4-Wire, wye),
correction
reducing output within 2% of nominal
Undervoltage
Maintains continuous operation without using battery power during brownout / undervoltage conditions to 96 / 166
correction
(3-Phase, 4-Wire, wye)
LEDS ALARMS & SWITCHES
LED Indicators
7 LED DISPLAY: AC input, bypass input, AC-DC charger, DC-AC inverter, AC output, bypass operation and battery
operation
Front panel LCD
SELECTABLE LCD DISPLAY: indicates a wide range of UPS operational and fault/warning conditions including
display
operational mode, alarm/shutdown conditions, input/output voltage/frequency, battery voltage, load percentage and
more (see manual)
Alarms
Alarms warn against a variety of operational conditions: low-battery, overload, shutdown, bypass and more
Alarm cancel
Power-fail alarm can be silenced using alarm-cancel switch
operation
SUBF2030
(holds 4 SURBC2030)
SUBF2030
SURBC2030
battery packs for extended runtime. Additional
and additional
SURBC2030
batteries - see runtime chart for

Advertisement