Summary of Contents for Tripp Lite SmartOnline 120/208V

  • Page 1: Table Of Contents

    7.1 Internal Battery Pack Wiring Diagram 8. Warranty & Warranty Registration 9. Specifications Español Français 1111 W. 35th Street • Chicago, IL 60609 USA (773) 869-1234 • www.tripplite.com Copyright © 2009 Tripp Lite. All rights reserved. SmartOnline™ is a trademark of Tripp Lite.
  • Page 2: Important Safety Warnings

    • Do not dispose of the batteries in a fire. The UPS batteries are recyclable. Refer to local codes for disposal requirements, or in the USA only, refer to these sources for recycling information: 1-800-SAV-LEAD (1-800-728-5323), 1-800-8-BATTERY (1-800-8-228-8379), or www.rbrc.com. • Internal batteries must be replaced by equivalent batteries available from Tripp Lite. • Do not operate your UPS without batteries.
  • Page 3: Control Panels

    2. Control Panels 2.1 Front Panel Note: Familiarize yourself with the location and function of the features on your UPS system before installing and operating it. This button turns the UPS System's inverter ON. “ON” Button: “OFF” Button: This button turns the UPS System's inverter OFF. Note: If the UPS System remains off for an extended period of time, it should be turned back on periodically to allow the internal batteries to recharge.
  • Page 4: Battery Access Panel (Cover Removed)

    One connector (internal, not shown) connects the battery module to the power module. The other connector (shown) connects the battery module to an additional optional battery module (not shown, available separately from Tripp Lite). The battery system connectors are only utilized when adding an additional battery module. Use of these connectors is outlined in the owner's manual included with the additional battery module.
  • Page 5: Rear Panel

    This female DB9 port connects your UPS to a workstation or server. It uses RS-232 communications to report UPS and power conditions. It is used with Tripp Lite software and an RS-232 Cable to monitor and manage network power and to automatically save open files and shut down equipment during a blackout.
  • Page 6: Installation

    3. Installation 3.1 UPS Location Move your UPS over short distances using its wheels. Note: The wheels are not designed to provide long-term support for the UPS system after final installation. Mounting bracket installation is required. 3.2 Mounting Bracket Installation DANGER! RISK OF PRODUCT DAMAGE AND SERIOUS PERSONAL INJURY The UPS System's wheels are not designed to provide long-term support for the UPS system after final...
  • Page 7: Initial Battery Charging

    3. Installation ( continued ) 3.4 UPS Input And Output Hardwire Connection WIRING CONNECTION Connect your wiring to the input and output terminal blocks located on the rear panel of your UPS (see figure below). CAUTION! Qualified personnel should follow all procedures prescribed by N.E.C. and other local codes for hardwiring devices to a utility source.
  • Page 8: Lcd Display Select Button

    4. Operation ( Normal Conditions ) 4.4 LCD Display Select Button Momentarily press the “SELECT” button on the front panel to browse through different power readings on the LCD Display. BYPASS OUTPUT R: XXXV R: XXX.XV (Bypass & Output Voltage) S: XXXV S: XXX.XV T: XXXV...
  • Page 9: Inverter On Warnings

    5. Operation ( Special Conditions ) 5.2 Inverter On Warnings When the inverter is ON, the LCD Display may show any one of the following warnings: Condition UPS Output Overload UPS Charger Failure Abnormal Input Frequency Abnormal Input Phase Battery is Depleting* Battery Charge is Nearly Depleted* * During a prolonged blackout, users should save files and shut down connected equipment.
  • Page 10: Communications

    6.1 RS-232 Interface This female DB9 port connects your UPS via an RS-232 cable to a workstation or server equipped with Tripp Lite software. The port uses RS-232 communications to report UPS status and power conditions. Using this port, Tripp Lite software can monitor and manage network power and automatically save open files and shut down equipment during a blackout.
  • Page 11: Remote Emergency Power Off (Epo)

    UPS off during battery installation. (See section 4.2, Turning the UPS Off.) Internal battery packs must be replaced by equivalent batteries available from Tripp Lite. Adding battery packs will increase recharge time. Individual models may vary slightly from diagrams.
  • Page 12: Internal Battery Pack Wiring Diagram

    7. Adding or Replacing Internal Batteries 7.1 Internal Battery Pack Wiring Diagram Qualified service personnel should familiarize themselves with the battery pack wiring diagram prior to adding or replacing batteries. The battery module can accept up to four battery packs (each pack consisting of two strings). The diagram shows all four battery packs connected for illustrative purposes only.
  • Page 13 7. Adding or Replacing Internal Batteries Place the UPS System in Bypass Mode or completely turn it off, depending on preference. (See section 5.4, Operation of Manual Bypass Switch, or 4.2, Turning the UPS Off.) Remove battery access panel, located on the FRONT of the UPS system.
  • Page 14 7. Adding or Replacing Internal Batteries Remove the fuse block bracket. Slide the battery string with the RED cable into an empty slot within the battery compartment as shown. Make sure that the string is oriented as shown in the diagram Note: If the auxiliary battery connector is in the way, remove its mounting screw and position the cable to allow adequate room to add the battery strings Slide the battery string with the BLACK cable next to it (on the left)
  • Page 15 The battery pack's Acceptable DC Voltage Range is between 220 and 280V DC. If several attempts at voltmeter tests yield results outside this range, contact Tripp Lite for assistance in determining the possible causes of the incorrect voltage reading.
  • Page 16: Warranty & Warranty Registration

    3-Phase UPS System Limited Warranty Seller warrants this product, if used in accordance with all applicable instructions as verified by Tripp Lite's "Start-up" service, to be free from original defects in material and workmanship for a period of one year (inside USA and Canada) from the date of purchase.
  • Page 17: Specifications

    43 x 28 x 44.5 in. Shipping Weight 609 lb. + Backup times are expandable with additional Battery Packs, sold separately. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice. Model: SU20K3/3XR5 Input...
  • Page 18 43 x 28 x 44.5 in. Shipping Weight 750 lb. + Backup times are expandable with additional Battery Packs, sold separately. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice. Model: SU30K3/3XR5 Input...