Specifications - Tripp Lite SmartOnline SU20K3/3XR5 Specifications

20kva on-line double-conversion ups, 3 phase input / output with oversize battery set
Hide thumbs Also See for SmartOnline SU20K3/3XR5:

Advertisement

Included internal batteries provide 42 minutes runtime at half load (8,000 watts) and 17 minutes runtime at full load (16,000 watts)
3:1 crest factor safely supports a variety of equipment, even those with wildly-fluctuating power demands
Extend runtime by installing optional internal battery packs (model # SURBC2030) through the front panel access door. SU20K3/3XR5
includes 5 internal battery packs and accepts 3 additional internal battery packs. A standalone battery module compartment with a 4 battery
pack capacity and daisy-chain capability (model # SUBF2030) is available to further extend runtime.
3 communication ports (RS-232, contact closure and AS-400)
Slot for optional SNMP card (model # SNMPWEBCARD)
Manual bypass switch as well as an automatic bypass function ensures 100% availability of connected equipment by safely passing
through AC power when the UPS system requires maintenance
Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval
Emergency Power Off button turns UPS output OFF and disables Bypass output
PowerAlert Universal UPS Power Management Software and 6 ft. communication cable included
Start-up service program is recommended to enhance the reliability of the installation
Built-in Emergency Power Off (EPO) interface supports remote emergency shutdown in large facilities
Combination LED/LCD display

Specifications

OUTPUT
Output Volt Amp
20000
Capacity (VA)
Output kVA
20
capacity (kVA)
Output Watt
16000
Capacity (watts)
Output kW capacity
16
Output power factor
0.8
Crest Factor
3:1
Nominal Output
120V; 208V; 3-Phase Wye
Voltage(s)
Supported
Frequency
50 / 60 Hz
compatibility
Output voltage
+/- 2%
regulation (line
mode)
Output voltage
+/- 2%
regulation (Battery
mode)
Built-in UPS output
Hardwire
receptacles
Output AC
Sine wave
waveform (AC
mode)
Output AC
Pure Sine wave
waveform (battery
mode)
INPUT
Rated input current
60A (per phase, online)
(at maximum load)