Panasonic External Presentation unit 1728 Technical Description page 11

Hide thumbs Also See for External Presentation unit 1728:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00290 Rev: 1
LED indicator
L1
Fire (Brand)
L2
Alarms queued
(Flera larm)
L3
Extinguishing
(Släckanläggning
aktiverad)
L4
Ventilation
(Brandventilation
aktiverad)
L5
Fire brigade tx
(Larmsändare
aktiverad)
L6
Operation (Drift)
Technical Description External Presentation unit 1728
Table of LED indicators:
Colour
Indicating
2 x Red
Blinking+
Buzzer
(interm.)
Cont. (no
buzzer)
2 x Red
Blinking
Cont.
Red
Cont.
Yellow
Cont.
Red
Cont.
Green
Cont.
NOTE! Regarding "L2", see also chapter "SW mode & Address
setting, page 11.
2
2-zone / address dependence.
3
The alarm devices have to be silenced via the c.i.e. or an ext. FBP.
4
Indicating the same way, as in the c.i.e. the Presentation unit is connected
to, i.e. by activated output(s) of the corresponding type alternatively an
activated input for the LED respectively.
Fire alarm. (Also indicating pre-
warning, co-incidence
/ heat alarm the same way as in the
c.i.e.)
Like blinking + alarm devices are
3
silenced
.
More than one alarm. Use push button
"Alarms queued" (P1) to scroll.
Like blinking + alarm devices are
3
silenced.
Outputs for Extinguishing equipment are
4
activated.
Outputs for (fire / smoke) ventilation
equipment are activated.
Output(s) for fire brigade tx (routing
equipment) is/are activated.
24 V DC is connected and the
communication with the c.i.e. is working
normally, i.e. the Ext. Presentation unit
is in operation.
9
2
and heavy smoke
4
4