Electrical And Physical Data - Rheem RA17 Series Installation Instructions Manual

Air cooled condensing units
Table of Contents

Advertisement

Electrical and Physical Data - cont.
Model
Number
Freq Rated Load
Voltage Phase
RA1724AJ2CB
208-230
1
60
RA1736AJ2CB
208-230
1
60
RA1748AJ2CB
208-230
1
60
RA1760AJ2CB
208-230
1
60
DIMENSIONAL DATA
RA17
Height "H" inches [mm]
Length "L" inches [mm]
Width "W" inches [mm]
ELECTRICAL
Compressor
Fan
Minimum
Motor
Circuit
Full
Locked Roto r
Load
Ampacity
Amperes
Amperes
Amperes
Amperes
(RLA)
(LRA)
(FLA )
11.7/11.7
58.3
1.40
15.3/15.3
83.0
1.20
21.2/21.2
104.0
5.30
28.8/28.8
152.9
5.30
UNIT MODEL NUMBER EXPLANATION
R A
17 24
A
J 2 C B
24
35 [889]
33.75 [857]
33.75 [857]
GENERAL INFORMATION
RA17
Fuse or HACR
Circuit Breaker
Face
Area
Maximum
Minimum
Sq. Ft .
Amperes
Amperes
[m
2
]
16/16
25/25
20/20
19.76 [1.84]
21/21
35/35
25/25
22.23 [2.07]
32/32
50/50
40/40
32.30 [3.00]
42/42
60/60
50/50
32.30 [3.00]
MINOR SERIES
TYPE
C - COMMUNICATING
TYPE
2 - TWO STAGE
VOLTAGE
J = 1 PH, 208-230/60
MAJOR SERIES
CAPACITY
24 = 24,000 BTU/HR [7.03 kW]
36 = 36,000 BTU/HR [10.55 kW]
48 = 48,000 BTU/HR [14.07 kW]
60 = 60,000 BTU/HR [17.58 kW]
SEER
CONDENSER
BRAND
36
39 [991]
33.75 [857]
33.75 [857]
PHYSICAL
Outdoor Coil
Refrig .
Per
Circuit
No.
CFM
(oz. )
Rows
[L/s]
[g]
1
5133 [2423]
128 [3629]
1
3540 [1671]
151 [4281]
1
4251 [2006]
204 [5783]
1
5133 [2423]
223 [6322]
48
60
51 [1295]
51 [1295]
35.75 [908]
35.75 [908]
35.75 [908]
35.75 [908]
Weight
Net
Shipping
Lbs.
Lbs. [kg]
[kg]
160 [72.6]
167 [75.7]
180 [81.6]
187 [84.8]
231 [104.8]
238 [108.0]
241 [109.3]
248 [112.5]
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ra1724aj2cbRa1736aj2cbRa1748aj2cbRa1760aj2cb