Active Compressor Protection Mode
Active Protection – Code 7 – Compressor open run circuit
If the ICC detects current in the start circuit
without current present in the run circuit, the
ICC will lockout the compressor to keep it from
continuing to operate and flash an
dual -segment
IMPORTANT:
protection must be manually reset.
Three are three methods to reset the ICC after an active
protection lockout:
NOTE:
The ICC will attempt to start the unit
when the TEST button is pressed and released
NOTE:
The preferred method of resetting the ICC
Test and Fault Recall Modes
Test Mode (Test Button on the ICC)
mode
operation
on the
Ds followed by a 0 .
This mode of active
command for unit operation is present, TEST mode
causes:
display
operate
show the current command for unit operation.
NOTE:
If a command for unit operation is present
at the end of TEST mode will cause the unit to continue
to operate.
mode causes
Note: Entering TEST mode without a command for unit
operation will cause the compressor to run 5-seconds.
Fault Recall Mode
FAULT RECALL mode by pressing the UP
and SELECT buttons at the same time with insulated
will clear fault history. 00 no faults or history has been
cleared
most recent fault. Continue to press UP to show other
alarms.
displayed first.
mode after displaying stored faults
INSTALLATION
FAULT RECALL
25