TABLE 1
(-)PNL ELECTRICAL AND PHYSICAL DATA
Model
Compressor
Phase
Number
Rated Load
Frequency (Hz)
(-)PNL-
Amperes
Voltage (Volts)
(RLA)
v. 12/16/2008
018JAZ
1-60-208/230
9/9
024JAZ
1-60-208/230
12.8/12.8
030JAZ
1-60-208/230
14.1/14.1
031JAZ
1-60-208/230
14.1/14.1
036CAZ
3-60-208/230
13.2/13.2
036DAZ
3-60-460
6
036JAZ
1-60-208/230
17.9/17.9
042CAZ
3-60-208/230
13.6/13.6
042DAZ
3-60-460
6.1
042JAZ
1-60-208/230
20.5/20.5
043CAZ
3-60-208/230
13.6/13.6
043DAZ
3-60-460
6.1
043JAZ
1-60-208/230
20.5/20.5
048CAZ
3-60-208/230
13.7/13.7
048DAZ
3-60-460
6.2
048JAZ
1-60-208/230
21.8/21.8
049CAZ
3-60-208/230
13.7/13.7
049DAZ
3-60-460
6.2
049JAZ
1-60-208/230
21.8/21.8
060CAZ
3-60-208/230
15.6/15.6
060DAZ
3-60-460
7.8
060JAZ
1-60-208/230
26.3/26.3
TABLE 2
(-)PPL ELECTRICAL AND PHYSICAL DATA
Model
Compressor
Phase
Number
Rated Load
Frequency (Hz)
(-)PPL-
Amperes
Voltage (Volts)
(RLA)
018JAZ
1-60-208/230
9/9
024JAZ
1-60-208/230
12.8/12.8
030JAZ
1-60-208/230
14.1/14.1
036JAZ
1-60-208/230
17.9/17.9
042JAZ
1-60-208/230
20.5/20.5
048JAZ
1-60-208/230
21.8/21.8
060JAZ
1-60-208/230
26.3/26.3
6
ELECTRICAL
Fan Motor
Minimum
Full Load
Circuit
Locked Rotor
Amperes
Ampacity
Amperes
(FLA)
Amperes
(LRA)
48
0.6
12/12
58.3
0.6
17/17
73
0.8
19/19
73
0.6
20/20
88
1.2
18/18
44
0.6
9
112
1.2
24/24
83.1
1.2
19/19
41
0.6
9
109
1.2
27/27
83.1
1
18/18
41
0.6
10
109
1
27/27
83.1
1.2
19/19
41
0.6
9
117
1.2
29/29
83.1
1
19/19
41
0.6
9
117
1
29/29
110
1.2
21/21
52
0.6
11
134
1.2
35/35
ELECTRICAL
Fan Motor
Minimum
Full Load
Circuit
Locked Rotor
Amperes
Ampacity
Amperes
(FLA)
Amperes
(LRA)
48
0.6
12/12
58.3
0.6
17/17
73
0.8
19/19
112
1.2
24/24
109
1.2
27/27
117
1.2
29/29
134
1.2
35/35

2.5 PROPER INSTALLATION

Proper sizing and installation of this equipment is critical to achieve optimal perfor-
mance. Use the information in this Installation Instruction Manual and reference the
applicable Engineering Specification Sheet when installing this product.
IMPORTANT: This product has been designed and manufactured to meet ENER-
®
GY STAR
criteria for energy efficiency when matched with appropriate coil compo-
nents. However, proper refrigerant charge and proper airflow are critical to achieve
rated capacity and efficiency. Installation of this product should follow the manufac-
turer's refrigerant charging and airflow instructions. Failure to confirm proper
charge and airflow may reduce energy efficiency and shorten equipment life.
Fuse or HACR
Outdoor Coil
Circuit Breaker
Minimum
Maximum
Face Area
Amperes
Amperes
Sq. Ft. (m
2
)
15/15
20/20
8.18 (0.76)
20/20
25/25
8.18 [0.76]
25/25
30/30
20.13 [1.87]
25/25
30/30
13 [1.21]
25/25
30/30
23.01 [2.14]
15
15
23.01 [2.14]
30/30
40/40
23.01 [2.14]
25/25
30/30
23.01 [2.14]
15
15
23.01 [2.14]
35/35
45/45
23.01 [2.14]
25/25
35/35
20.1 [1.87]
15
15
20.1 [1.87]
35/35
45/45
20.1 [1.87]
25/25
30/30
23.01 [2.14]
15
15
23.01 [2.14]
35/35
50/50
23.01 [2.14]
25/25
30/30
20.1 [1.87]
15
15
20.1 [1.87]
35/35
50/50
20.1 [1.87]
25/25
35/35
23.01 [2.14]
15
15
23.01 [2.14]
45/45
60/60
23.01 [2.14]
Fuse or HACR
Outdoor Coil
Circuit Breaker
Minimum
Maximum
Face Area
Amperes
Amperes
Sq. Ft. (m
2
)
15/15
20/20
8.18 [0.76]
20/20
25/25
8.18 [0.76]
25/25
30/30
12.87 [1.2]
30/30
40/40
23.01 [2.14]
35/35
45/45
23.01 [2.14]
35/35
50/50
23.01 [2.14]
45/45
60/60
44 [4.09]
PHYSICAL
Refrig.
Per
Circuit
No.
CFM
Oz. [g]
Rows
[L/s]
Lbs. [kg]
1
1925 [908]
83 [2353]
155 [70.3]
1
1925 [908]
86 [2438]
155 [70.3]
1
2650 [1251]
133 [3771]
200 [90.7]
1
1925 [908]
101 [2863]
164.5 [74.6] 174.5 [79.2]
1
3575 [1687]
145 [4111] 246.5 [111.8] 256.5 [116.3]
1
3575 [1687]
145 [4111] 246.5 [111.8] 256.5 [116.3]
1
3575 [1687]
145 [4111] 246.5 [111.8] 256.5 [116.3]
1
3575 [1687]
160 [4536]
257 [116.6]
1
3575 [1687]
160 [4536]
257 [116.6]
1
3575 [1687]
160 [4536]
257 [116.6]
1
2650 [1251]
168 [4763]
227 [103]
1
2650 [1251]
168 [4763]
227 [103]
1
2650 [1251]
168 [4763]
227 [103]
1
3575 [1687]
160 [4536]
246 [111.6]
1
3575 [1687]
160 [4536]
246 [111.6]
1
3575 [1687]
160 [4536]
246 [111.6]
1
2650 [1251]
157 [4451]
229 [103.9]
1
2650 [1251]
157 [4451]
229 [103.9]
1
3575 [1687]
157 [4451]
229 [103.9]
1
3350 [1581]
242 [6861]
260 [117.9]
1
3350 [1581]
242 [6861]
260 [117.9]
1
3350 [1581]
242 [6861]
260 [117.9]
PHYSICAL
Refrig.
Per
Circuit
No.
CFM
Oz. [g]
Rows
[L/s]
Lbs. [kg]
1
1925 [908]
83 [2353]
156 [70.8] 166 [75.3]
1
1925 [908]
86 [2438]
156 [70.8] 167 [75.8]
1
1925 [908]
101 [2863]
175 [79.4] 186 [84.4]
1
3575 [1687]
145 [4111] 246 [111.6] 256 [116.1]
1
3575 [1687]
160 [4536] 256 [116.1] 266 [120.7]
1
3575 [1687]
160 [4536]
258 [117] 268 [121.6]
1
3100 [1463]
277 [7853] 308 [139.7] 318 [144.2]
Weight
Net
Shipping
Lbs. [kg]
165 [74.8]
165 [74.8]
210 [95.3]
267 [121.1]
267 [121.1]
267 [121.1]
237 [107.5]
237 [107.5]
237 [107.5]
256 [116.1]
256 [116.1]
256 [116.1]
239 [108.4]
239 [108.4]
239 [108.4]
270 [122.5]
270 [122.5]
270 [122.5]
Weight
Net
Shipping
Lbs. [kg]