Diagnostics And Troubleshooting; Fault Recall Procedure; Compressor/Fan Motor Test Mode; Defrost Test Mode - Rheem ECONET RP2024BJVCA Installation Instructions Manual

Ariable speed r-410a heat pump outdoor units
Table of Contents

Advertisement

Advanced operating status and diagnostic
information is available through the Variable Speed
Outdoor Control dual 7-segment display and the
EcoNet
Control Center that greatly enhances the
TM
ability to quickly and accurately diagnose system
faults. The following sections provide details for
the fault codes plus additional troubleshooting
information to assist the service technician.
9.1 Fault Recall
Procedure
Fault codes can be recalled using the EcoNet
Control Center service menu or by using the
Variable Speed Outdoor Control (VSODC) menu.
The EcoNet
Control Center service menu is by
TM
far the best method as it provides additional fault
codes and greater detail that can be used when
diagnosing the system.
To access the EcoNet
Control Center service
TM
menu, select SERVICE on the screen and navigate
to the fault code section to retrieve any fault codes
that have been stored.
To access fault codes on the VSODC, press the
SW2 and TEST buttons at the same time for at
least 8 seconds and release. FC (Fault Codes) will
be displayed on the dual 7-segment display as the
first menu item. Press the SW2 button to display
the first fault code that was stored. Continue
pressing the SW2 button to retrieve additional fault
codes in the order they were stored.
TEST button to return to the main menu.
9.2 Compressor/
Fan Motor Test Mode
A test mode is provided on the Varible Speed
Outdoor Control (VSODC) to determine if
the compressor and outdoor fan motor are
operational.
• Enter TEST mode by pressing the TEST button
on the VSODC with an insulated probe for one (1)
second and release.
• The TEST mode causes the VSODC to do the
following:
1) Resets the 5-minute anti-short-cycle timer.
2) Energizes the unit without a call for unit
operation.
• If the 5-minute anti-short-cycle timer or
30-second minimum run timer is active (a
flashing "c," "C," "h," or "H" is displayed on
the dual 7-segment LEDs) and a call for unit
operation is present, the TEST mode causes:
1) A "t" to display momentarily on the dual
7-segment display.
9.0 DIAGNOSTICS & TROUBLESHOOTING
TM
Press the
2) The compressor will start and the outdoor fan
will operate.
3) The display will change to a steady "c," "C,"
"h," or "H" to show the current demand for
unit operation.
NOTICE:
If a call for unit operation is
present at the end of the TEST mode, the unit will
continue to operate.
• If no call for unit operation is present, the TEST
mode causes:
1) A steady "C" to appear on the dual
7-segment LEDs.
2) The compressor will start.
3) The compressor will turn off after 5 seconds.
NOTICE:
Entering TEST mode
without a call for unit operation will cause the
compressor to run for 5 seconds.

9.3 Defrost Test Mode

Normal Defrost Test Mode: A defrost test mode
can be initiated by pressing the TEST button
on the VSODC for 1 second when the system
is operating in the heating mode. Upon release
of the TEST button, the system will initiate a
defrost cycle until the coil temperature reaches
the termination temperature or 14 minutes have
elapsed. The coil temperature must be below
70°F [21.1°C] or the system will not initiate a
defrost test. A "d" will appear on the VSODC
display indicating the system is in the defrost
mode. Pressing the TEST button while the system
in in the Defrost Test Mode will terminate the test
mode. If the system initiates and terminates the
defrost cycle normally, the system is working
properly. Termination of the defrost cycle after
the 14 minute maximum time is very unusual
and typically indicates a problem with the coil
temperature thermistor or it's wiring connections.
Continuous Defrost Test Mode: The VSODC
can be forced into a continuous defrost mode
by holding the TEST button down for at least
5 seconds and releasing when the system is in
the heating mode. The system will remain in the
defrost mode until the TEST button is pressed
again. If the system is left in this mode for too
long, the High Pressure Control will trip and shut
the system down.