Installing Fan 3 (A914-Pwr-Fan) - Cisco ASR 914 Manual

Hide thumbs Also See for ASR 914:
Table of Contents

Advertisement

Replacing the Fan Tray
Replacing the Fan Tray
The fan tray supports online insertion and removal (OIR). There is no need to power down the Cisco ASR
914 Router to remove or replace the fan tray. Only one fan tray can be removed or replaced at a time. However,
the router will shut down if the fan tray is removed for more than 5 minutes at 30º C. If more than one fan
tray is removed the system will shut down immediately. Once the thermal overload condition is absent, the
system attempts to power up automatically, if the fan tray is re-inserted and the system temperature is within
limits. Approximately at 25º C the system powers back in 2 minutes.
Note
Do not introduce body parts or objects in the fan tray slot when installing or removing the fan tray module.
Exposed circuitry is an energy hazard.
Caution
The router can stay active for up to 60 seconds if the temperature is below the ambient limit. However, in the
event of an overtemperature alarm, the router can shut down in less than 60 seconds. In the event of a critical
temperature alarm, the router shuts down immediately.
Caution
To avoid erroneous failure messages, allow at least 2 minutes for the system to reinitialize after the fan tray
has been removed or replaced.

Installing Fan 3 (A914-PWR-FAN)

Procedure
Step 1
Insert Fan 3 into the chassis until it is firmly seated.
Installing the Cisco ASR 914 Router
14
Installing the Cisco ASR 914 Router

Advertisement

Table of Contents
loading

Table of Contents