4.5

Terminal strip X9

Terminal strip X9 is used to connect an external 24 VDC power supply and to connect a
main or bypass contactor.
Fault and alarm signals can be connected to the digital inputs. The digital output allows, for
example, an external rectifier to be controlled.
The external 24 VDC power supply must be connected if the inverter is connected to the line
supply via a main contactor (to start the Control Unit).
The power supply should be located directly next to the inverter (e.g. in the same cabinet).
The cable length to terminal X9 must not exceed 30 m.
Terminal Name
1
P24
2
M
3
External alert
4
External fault
5
Stop 0
6
Stop 1
7
M
8
DC link
charged
9
NC
10
NC
Power Module PM330
Hardware Installation Manual, 12/2018, A5E32844552B AF
Meaning
In-
put/output
External power sup-
In-
ply
put/output
1)
Electronics ground
Reference
External alarm
Input
External fault
Input
OFF 2
Input
OFF 3
Input
Reference
Feedback signal,
Output
"U
charged"
DC link
Not connected
Not connected
Technical data
As input:
24 V DC (20.1 ... 28.8 V)
Current consumption: max. 2 A
As output:
Load at X9:1 and X9:8 together: Max. 250 mA
Overcurrent trip with restart attempt every 3.5 sec.
Voltage: -3 V ... +30 V
Current consumption:
6.4 mA at 24 VDC
1.3 mA at <5 V
4 mA at 15 V
8 mA at 30 V
Level (including ripple):
High level: 15 V ... 30 V
Low level: -3 V ... +5 V
Voltage: 24 V DC
for external supply via X9:1/2:
max. load current: 500 mA
without external supply via X9:1/2:
Load at X9:1 and X9:8 together: max. 250 mA
continuously short-circuit proof
The output current is taken from the supply at X9, ter-
minal 1.
Connecting up, switching on
4.5 Terminal strip X9
49