Connecting up, switching on
4.2 Line, motor and DC link connection
Frame size JX
The diagram shows the
layout of line and motor
terminals and terminal strip
X9.
For frame size JX, only
connection from the top or
bottom is possible.
Tightening torques for the
line, motor and PE termi-
nals (M12): 50 Nm
The cable entry protection
for the line connection (
must be broken out corre-
sponding to the diameter of
the cable to be introduced.
The cable entry protection
for the motor connection is
described in the following
section.
After connection, the co-
vers of the line and motor
terminals must be rein-
stalled (tightening torque:
6 Nm).
In order to ensure a uni-
form current distribution,
first connect the motor ca-
ble to the upper connection
points.
Only use the lower connec-
tion points if the upper con-
nection points have been
assigned.
For each phase, ensure the
best possible symmetrical
distribution of the motor
cables.