Vi-Controls Interface - Trane R Series Installation Operation & Maintenance

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

61

VI-Controls Interface

CH530 Communications Overview
The Trane CH530 control system that
runs the chiller consists of several
elements:
The main processor collects
data, status, and diagnostic information
and communicates commands to the
starter module and the LLID (for Low
Level
Intelligent
Device)
main processor has an integral display
(DynaView).
Higher
level
modules
starter) exist only as necessary to
support
system
level
communications. The starter module
provides control of the starter when
starting, running, and stopping the
chiller motor. It also processes its own
diagnostics and provides motor and
compressor protection.
Low level intelligent device
(LLID)
bus.
The
main
communicates to each input and output
device (e.g. temperature and pressure
sensors, low voltage binary inputs,
analog
input/output)
all
to a four-wire bus, rather than the
conventional
control
architecture
signal wires for each device.
The communication interface to
a building automation system (BAS).
A service tool to provide all
service/maintenance capabilities.
Main
processor
and
(TechView) software is downloadable
from www.Trane.com. The process is
discussed later in this section under
TechView Interface.
DynaView provides bus management.
It has the task of restarting the link, or
filling in for what it sees as "missing"
devices when normal communications
has been degraded. Use of TechView
may be required.
The CH530 uses the IPC3 protocol
based on RS485 signal technology
and communicating at 19.2 Kbaud to
allow 3 rounds of data per second on
a 64-device network. A typical four
compressor RTAC will have around 50
devices.
Most diagnostics are handled by the
DynaView. If a temperature or pressure
bus.
The
is reported out of range by a LLID, the
DynaView processes this information
and calls out the diagnostic. The
individual LLIDs are not responsible
(e.g.
for any diagnostic functions. The only
control
and
exception to this is the Starter module.
NOTE: It is imperative that the CH530
Service Tool (TechView) be used to
facilitate the replacement of any LLID
or reconfigure any chiller component.
TechView is discussed later in this
section.
Controls Interface
processor
Each
chiller
DynaView interface. The DynaView
has the capability to display information
connected
to the operator including the ability
to adjust settings. Multiple screens
of
are available and text is presented in
multiple languages as factory-ordered
or can be easily downloaded from www.
trane.com.
TechView can be connected to either
the DynaView module and provides
further data, adjustment capabilities,
diagnostics
service
tool
downloadable software.
DynaView Interface
The
DynaView
enclosure design: weatherproof and
durable plastic for use as a stand-alone
device on the outside of the unit or
mounted nearby.
The display on DynaView is a 1/4 VGA
display with a resistive touch screen
and an LED backlight. The display area
is approximately 4 inches wide by 3
inches high (102mm x 60mm).
is
equipped
with
a
information
using
share
the
same
RTAC-SVX002A-EN