Vii-Diagnostics - Trane R Series Installation Operation & Maintenance

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Tab. VI-01 – Setpoints View Items
Hex
Diagnostic Name and
Code
Source
398
BAS Communication Lost Special
390
BAS Failed to Establish
2E6
Check Clock
8A
Chilled Water Flow
(Entering
5EF
Comm Loss: Chilled
Water Flow Switch
5F2
Comm Loss: Cond Rfgt
694
Comm Loss: Electronic
Expansion Valve, Circuit
#1
695
Comm Loss: Electronic
Expansion Valve, Circuit
#2
5DE
Comm Loss: Emergency
Stop
68E
Comm Loss: Evap Oil
Return Valve, Cprsr 1A
69E
Comm Loss: Evap Oil
Return Valve, Cprsr 1B
68F
Comm Loss: Evap Oil
Return Valve, Cprsr 2A
69F
Comm Loss: Evap Oil
Return Valve, Cprsr 2B
5E4
Comm Loss: Evaporator
Entering Water
Temperature
5E3
Comm Loss: Evaporator
Leaving Water
Temperature
6BB
Comm Loss: Evaporator
Rfgt Drain Valve - Ckt 1
6BC
Comm Loss: Evaporator
Rfgt Drain Valve - Ckt 2
688
Comm Loss: Evaporator
Rfgt Liquid Level, Circuit
#1
689
Comm Loss: Evaporator
Rfgt Liquid Level, Circuit
#2
5F0
Comm Loss: Evaporator
Rfgt Pressure, Circuit #1
5F1
Comm Loss: Evaporator
Rfgt Pressure, Circuit #2
RTAC-SVX002A-EN

VII-Diagnostics

Severity
Persistence
NonLatch
The BAS was setup as "installed" at the MP and the Comm 3 LLID lost
communications with the BAS for 15 contiguous minutes after it had been
established. Refer to Section on Setpoint Arbitration to determine how
setpoints and operating modes may be effected by the comm loss. The
chiller follows the value of the Tracer Default Run Command which can
be previously written by Tracer and stored nonvolatilely by the MP (either
use local or shutdown).
Special
NonLatch
The BAS was setup as "installed" and the BAS did not communicate with
the MP within 15 minutes after power-up. Refer to Section on Setpoint
Arbitration to determine how setpoints and operating modes may be
effected. Note: The original requirement for this was 2 minutes, but was
implemented at 15 minutes for RTAC
Info
Latch
The real time clock had detected loss of its oscillator at some time in
the past. This diagnostic can be effectively cleared only by writing a new
value to the chiller's time clock using the TechView or DynaView's
"set chiller time" functions.
Info
NonLatch
The entering evaporator water temp fell below the leaving evaporator
water temp. by more than 2°F for 100 °F-sec. For RTAC this diagnostic
cannot reliably indicate loss of flow, but can warn of improper flow
direction through the evaporator, misbound temperature sensors, or
other system problems
Latch
Continual loss of communication between the MP and the Immediate
Functional ID has occurred for a 30 second period.
Pressure,
Circuit #1
Immediate Latch Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch Remote
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch Remote
Normal
Latch S
Same as Comm Loss: Chilled Water Flow Switch Remote Stop
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch Remote
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Special
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Immediate
Latch
Same as Comm Loss: Chilled Water Flow Switch
Immediate
Latch
Same as Comm Loss: Chilled Water Flow Switch
Immediate
Latch
Continual loss of communication between the MP and he Functional ID
has occurred for a 30 second period.
Note: This diagnostic is replaced by diagnostic 5FB below with Rev 15.0
Immediate
Latch
Continual loss of communication between the MP and the Functional ID
has occurred for a 30 second period. Note: This diagnostic is replaced
by diagnostic 5FD below with Rev 15.0
Criteria
Reset Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
82