Dry Coil Delta P - York Predator XP Series Installation Manual

Hide thumbs Also See for Predator XP Series:
Table of Contents

Advertisement

998659-YIM-C-0614
NOTE: The tubes must be inserted and held in position
perpendicular to the airflow so that velocity pressure
will not affect the static pressure readings.
3.
Use an Inclined Manometer or Magnehelic to determine
the pressure drop across the unit. This is the External
Static Pressure (ESP). In order to obtain an accurate
measurement, be certain that the air filters are clean.
4.
Determine the number of turns the variable motor sheave
is open.
5.
Select the correct blower performance table for the unit
from Tables 14 and 15. Tables are presented for side and
downflow configuration.
6.
Determine the unit Measured CFM from the Blower
Performance Table, External Static Pressure and the
number of turns the variable motor sheave is open.
Figure 29: Dry Coil Delta P
40
0.5
0.45
0.4
0.35
0.3
0.25
0.2
0.15
0.1
0.05
0
1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500
7.
To adjust Measured CFM to Required CFM, see SUPPLY
AIR DRIVE ADJUSTMENT.
8.
After reading has been obtained, remove the tubes and
seal holes.
9.
Tighten blower pulley and motor sheave set screws after
any adjustments. Re-check set screws after 10-12 hrs. run
time is recommended.
NOTE: With the addition of field installed accessories repeat
this procedure.
Failure to properly adjust the total system air quantity
can result in extensive blower damage.
XP078
XP090
Airflow (CFM)
XP102
XP120
XP150
Johnson Controls Unitary Products