998659-YIM-C-0614
• Press the  button to increase (change) the displayed
1
parameter value.
• Press the  button to decrease (change) the displayed
parameter value.
• Press the  button to accept the displayed value and
store it in non-volatile RAM.
• CHANGE STORED displays.
• Press the  button (MenuUp/Exit) to return to the
previous menu.
Menu Structure
The Menus in display order are:
• STATUS
• SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
• ALARMS
1. When values are displayed, pressing and holding the  and
button causes the display to automatically increment.
ECONOMIZING
AVAILABLE
NOT AVAILABLE
TEMPERATURE
Figure 26: Single Enthalpy Curve And Boundaries
Table 11: Single Enthalpy and Dual Enthalpy High Limit Curves.
Enthalpy
Temp.
Curve
Dry-Bulb (°F)
ES1
80.0
ES2
75.0
ES3
70.0
ES4
65.0
ES5
60.0
HL
86.0
30
Temp.
Enthalpy
Dewpoint (°F)
(btu/lb/da)
60.0
28.0
57.0
26.0
54.0
24.0
51.0
22.0
48.0
20.0
66.0
32.4
NOTE: Your menu parameters will be different depending on
your configuration. See the JADE™ Economizer
Module accessory instruction P/N 1150208-UAI-A-0514
included in this instruction packet for additional menu
information.
Economizer Setup And Configuration
Before being placed into service, the JADE™ Economizer
module must be setup and configured for the installed system.
NOTE: During setup, the Economizer module is live at all
times.
The setup process uses a hierarchical menu structure that is
easy to use. You press the  and  arrow buttons to move
forward and backward through the menus and press the 
button to select and confirm setup item changes.
Time-out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status items.
Each Status items displays in turn and cycles to the next item
after 5 seconds.
P2 (T,RH)
ES5
Point P1
Temp. °F
Humidity %RH
80.0
36.8
75.0
39.6
70.0
42.3
65.0
44.8
60.0
46.9
86.0
38.9
DUAL ENTHALPY
HIGH LIMIT
SINGLE ENTHALPY
P1 (T,RH)
ES4
ES3
ES2
ES1
Point P2
Temp. °F
Humidity %RH
66.3
80.1
63.3
80.0
59.7
81.4
55.7
84.2
51.3
88.5
72.4
80.3
Johnson Controls Unitary Products