Additional Static Resistance - York Predator XP Series Installation Manual

Hide thumbs Also See for Predator XP Series:
Table of Contents

Advertisement

998659-YIM-C-0614
Table 20: Additional Static Resistance
Size
Model
CFM
(Tons)
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
078 (6.5)
3900
090 (7.5)
102 (8.5)
XP
4100
120 (10)
4300
150 (12.5)
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
1. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
2. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
42
1 2
Economizer
4" Filter
0.02
0.12
0.02
0.13
0.04
0.14
0.11
0.16
0.18
0.17
0.25
0.19
0.31
0.20
0.37
0.22
0.43
0.26
0.49
0.27
0.54
0.29
0.58
0.32
0.65
0.35
0.69
0.38
0.74
0.41
0.78
0.44
0.82
0.47
0.86
0.51
0.89
0.55
0.93
0.58
0.96
0.62
0.98
0.67
1.01
0.71
Electric Heat kW
2
9
18
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.12
0.13
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23
0.24
0.25
0.26
0.28
0.29
0.30
0.31
0.33
0.34
0.35
0.37
0.38
0.40
0.41
0.43
0.44
0.46
0.47
0.49
0.50
0.53
1
24
36
54
0.07
0.08
0.10
0.08
0.09
0.11
0.09
0.10
0.13
0.10
0.11
0.14
0.12
0.13
0.16
0.13
0.14
0.18
0.15
0.16
0.20
0.17
0.18
0.22
0.19
0.20
0.24
0.21
0.22
0.26
0.23
0.24
0.28
0.25
0.26
0.31
0.28
0.29
0.34
0.30
0.31
0.37
0.33
0.34
0.40
0.35
0.37
0.43
0.38
0.40
0.46
0.41
0.43
0.49
0.44
0.46
0.53
0.47
0.49
0.56
0.50
0.53
0.59
0.53
0.56
0.62
0.56
0.59
0.65
Johnson Controls Unitary Products