York PREDATOR XP Series Technical Manual

York PREDATOR XP Series Technical Manual

R-410a 6-1/2 thru 12-1/2 ton, 60 hertz
Hide thumbs Also See for PREDATOR XP Series:

Advertisement

TECHNICAL GUIDE
R-410A
XP SERIES
6-1/2 THRU 12-1/2 TON
60 Hertz
6-1/2 THROUGH 10 TON
12-1/2 TON
®
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Description

ASHRAE 90.1 COMPLIANT
®
®
YORK
Predator
units are convertible single packages with a
common footprint cabinet and common roof curb for all 6-1/2
through 12-1/2 ton models. All units have two compressors with
independent refrigeration circuits to provide 2 stages of cooling.
The units were designed for light commercial applications and
can be easily installed on a roof curb, slab, or frame.
®
All Predator
units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
All units are convertible between side and down airflow.
Independent economizer designs are used on side and down
discharge applications, as well as all tonnage sizes.
®
Predator
XP units are available in the following configurations:
heat pump and heat pump with electric heat. Electric heaters
are available as factory-installed options or field-installed
accessories.
Tested in accordance with:
528195-YTG-I-0513

Advertisement

Table of Contents
loading

Summary of Contents for York PREDATOR XP Series

  • Page 1: Description

    TECHNICAL GUIDE Description ASHRAE 90.1 COMPLIANT ® ® YORK Predator units are convertible single packages with a common footprint cabinet and common roof curb for all 6-1/2 through 12-1/2 ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling.
  • Page 2: Table Of Contents

    528195-YTG-I-0513 Table of Contents Description ................... . 1 Table of Contents .
  • Page 3: Nomenclature

    528195-YTG-I-0513 Nomenclature ® 6.5-12.5 Ton York Model Number Nomenclature X P 090 C00 A 2 A AA 6 0 1 2 4 A Product Category Product Style X = HP, Single Pkg., R-410A A = Style A B = Style B...
  • Page 4: Features And Benefits

    528195-YTG-I-0513 Features and Benefits • Advanced Controls - Simplicity® control boards have standardized a number of features previously available Standard Features only as options or by utilizing additional controls. • High Efficiency – High efficiency units reach as high as •...
  • Page 5 With a dual input kit installed, the economizer Factory Installed Options control compares the values of the two enthalpy or ® YORK offers several equipment options factory installed, for temperature inputs and positions the dampers to ® line.
  • Page 6 • BAS - Building Automation System Controls Simplicity ® ® • Disconnect Switch - For heat pump units with electric INTELLI-Comfort II™ Control - The York Simplicity heat, a HACR breaker sized to the unit is provided. For INTELLI-Comfort II™ control is factory installed. It includes...
  • Page 7 528195-YTG-I-0513 • York Commercial Comfort System (YCCS) - Provides • Manual Outdoor Air Damper - Like the motorized outdoor rooftop system integration for YCCS single zone and air damper, each manual outdoor air damper includes a change-over bypass systems. slide-in damper assembly with an outdoor air hood and filters.
  • Page 8 528195-YTG-I-0513 Accessories Part Number Description 1RC0470 Roof Curb, 8" Height 1RC0471 Roof Curb, 14" Height 1RC0472 Roof Curb, Transition (7.5 T through 12.5 T) 1BD0408 Burglar Bars, Downflow 2TP04520925 Electric Heat 9kW 230V 2TP04521825 Electric Heat 18kW 230V 2TP04522425 Electric Heat 24kW 230V 2TP04523625 Electric Heat 36kW 230V 2TP04525425...
  • Page 9: Guide Specifications

    ® vice factor. Units shall be designed to operate within the service Products in an ISO 9001 certified facility. YORK® Predator factor. Fan wheel shall be double inlet type with forward curve units are convertible single packages with a common footprint...
  • Page 10 528195-YTG-I-0513 Unit Controls: FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be made available by either/or): a. Unit shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker on • ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER the 24-volt transformer side. –...
  • Page 11 528195-YTG-I-0513 • DIRTY FILTER SWITCH – This kit includes a differential OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE pressure switch that energizes the fault light on the unit • ROOF CURB - 14” and 8” high, full perimeter knockdown thermostat, indicating that there is an abnormally high- curb, with hinged design for quick assembly.
  • Page 12: Physical Data

    528195-YTG-I-0513 Physical Data XP078-150 Physical Data Models Component XP078 XP090 XP102 XP120 XP150 Nominal Tonnage 12.5 AHRI COOLING PERFORMANCE Gross Capacity @ AHRI A point (Mbh) 80000 92550 105600 122000 158300 AHRI net capacity (Mbh) 78000 90000 102000 117000 150000 11.5 11.2 11.2...
  • Page 13 528195-YTG-I-0513 XP078-150 Physical Data (Continued) Models Component XP078 XP090 XP102 XP120 XP150 Nominal Tonnage 12.5 CONDENSER FAN DATA Quantity of Fans Fan diameter (Inch) Type Prop Prop Prop Prop Prop Drive Type Direct Direct Direct Direct Direct Quantity of motors Motor HP each No.
  • Page 14: Capacity Performance

    528195-YTG-I-0513 Capacity Performance XP078-150 Cooling Capacities XP078 (6.5 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh)
  • Page 15 528195-YTG-I-0513 XP078 (6.5 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW) (°F) 115°F...
  • Page 16 528195-YTG-I-0513 XP090 (7.5 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW) (°F) 75°F 85°F...
  • Page 17 528195-YTG-I-0513 XP090 (7.5 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW) (°F) 115°F...
  • Page 18 528195-YTG-I-0513 XP102 (8.5 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW) (°F) 75°F 85°F...
  • Page 19 528195-YTG-I-0513 XP102 (8.5 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW) (°F) 115°F...
  • Page 20 528195-YTG-I-0513 XP120 (10 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW) (°F) 75°F 85°F...
  • Page 21 528195-YTG-I-0513 XP120 (10 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW) (°F) 115°F...
  • Page 22 528195-YTG-I-0513 XP150 (12.5 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW) (°F) 75°F 85°F...
  • Page 23 528195-YTG-I-0513 XP150 (12.5 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW) (°F) 115°F...
  • Page 24 528195-YTG-I-0513 XP078-150 Heating Capacities XP078-150 Air Over Evaporator Size Capacity & Outdoor Temperature (°F @ 72% RH) Coil Model (Tons) DB (°F) 10.1 21.7 33.3 44.8 56.4 68.0 79.5 91.1 4.10 4.30 4.50 4.70 4.89 5.09 5.29 5.49 16.4 28.0 39.5 51.1 62.7...
  • Page 25 528195-YTG-I-0513 XP078-150 (Continued) Air Over Evaporator Size Capacity & Outdoor Temperature (°F @ 72% RH) Coil Model (Tons) DB (°F) 51.3 63.5 75.7 87.9 100.1 112.3 124.5 136.7 5.35 5.59 5.83 6.07 6.31 6.55 6.79 7.03 40.6 52.8 65.0 77.2 89.4 101.6 113.8...
  • Page 26: Airflow Performance

    528195-YTG-I-0513 Airflow Performance XP078-150 Side Duct Application XP078 (6.5 Ton) Side Duct Available External Static Pressure - IWG Air Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 HP &...
  • Page 27 528195-YTG-I-0513 XP120 (10 Ton) Side Duct Available External Static Pressure - IWG Air Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP & Field Supplied Drive Standard 2 HP &...
  • Page 28 528195-YTG-I-0513 XP078-150 Bottom Duct Application XP078 (6.5 Ton) Bottom Duct Available External Static Pressure - IWG Air Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 HP & Drive Hi Static 2 HP &...
  • Page 29 528195-YTG-I-0513 XP120 (10 Ton) Bottom Duct Available External Static Pressure - IWG Air Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP & Field Supplied Drive Standard 2 HP &...
  • Page 30 528195-YTG-I-0513 Additional Static Resistance Electric Heat kW Size Model Economizer 4” Filter (Tons) 1900 0.02 0.12 0.05 0.06 0.07 0.08 0.10 2100 0.02 0.13 0.06 0.07 0.08 0.09 0.11 2300 0.04 0.14 0.07 0.08 0.09 0.10 0.13 2500 0.11 0.16 0.08 0.09 0.10...
  • Page 31 528195-YTG-I-0513 Drive Selection Determine side or bottom supply duct Application. Determine desired airflow. Calculate or measure the amount of external static pressure. Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table.
  • Page 32 528195-YTG-I-0513 Altitude/Temperature Correction Factors Altitude (Ft.) Temp. 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 1.019 0.982 0.948 0.913...
  • Page 33: Sound Performance

    528195-YTG-I-0513 Indoor Blower Specifications Motor Motor Sheave Blower Sheave Size Model Datum Dia. Datum Dia. Belt (Tons) Eff. Frame Bore (in.) Model Bore (in.) Model (in.) (in.) 1-1/2 1725 1.15 2.4 - 3.4 VL40 AK84 (6.5) 1725 1.15 2.8 - 3.8 VL44 AK71 1-1/2...
  • Page 34 528195-YTG-I-0513 Outdoor Sound Power Levels Octave Band Centerline Frequency (Hz) Size Sound Rating Model (Tons) dB (A) 1000 2000 4000 8000 88.0 82.5 81.5 78.0 73.0 69.0 62.0 (6.5) 89.5 83.5 82.0 78.0 72.5 68.0 60.5 (7.5) 89.0 84.5 81.5 78.0 72.5 68.5...
  • Page 35: Electrical Data

    528195-YTG-I-0513 Electrical Data XP078-150 Standard Motor - Without Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size Pwr Exh (Amps) (Amps)
  • Page 36 528195-YTG-I-0513 XP078-150 Standard Motor - Without Powered Convenience Outlet (Continued) OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size Pwr Exh (Amps) (Amps) RLA LRA MCC...
  • Page 37 528195-YTG-I-0513 XP078-150 Hi Static Motor - Without Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps) RLA LRA...
  • Page 38 528195-YTG-I-0513 XP078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued) OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps)
  • Page 39 528195-YTG-I-0513 XP078-150 Standard Motor - With Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps) RLA LRA Model...
  • Page 40 528195-YTG-I-0513 XP078-150 Standard Motor - With Powered Convenience Outlet (Continued) OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps) RLA LRA...
  • Page 41 528195-YTG-I-0513 XP078-150 Hi Static Motor - With Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps) RLA LRA...
  • Page 42 528195-YTG-I-0513 XP078-150 Hi Static Motor - With Powered Convenience Outlet (Continued) OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps)
  • Page 43: Typical Wiring Diagrams

    528195-YTG-I-0513 Typical Wiring Diagrams XP078-150 Typical Wiring Diagrams Typical XP078-120 Heat Pump with/without Electric Heat Wiring Diagram Johnson Controls Unitary Products...
  • Page 44 528195-YTG-I-0513 Typical XP150 Heat Pump with/without Electric Heat Wiring Diagram Johnson Controls Unitary Products...
  • Page 45: Weights And Dimensions

    528195-YTG-I-0513 Weights and Dimensions XP078-150 Unit Weights Unit 4 Point Load Weight Unit 6 Point Load Weight FRONT FRONT LEFT LEFT FRONT LEFT Size Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.) Model (Tons) Shipping Operating 1085...
  • Page 46 528195-YTG-I-0513 XP078-150 Unit Dimensions XP078-120 XP150 Johnson Controls Unitary Products...
  • Page 47 528195-YTG-I-0513 XP078-150 Unit Physical Dimensions Dimension (in.) Unit Model Number 50 3/4 30 3/16 24 3/16 17 3/16 6 3/16 50 3/4 30 3/16 24 3/16 17 3/16 6 3/16 50 3/4 30 3/16 24 3/16 17 3/16 6 3/16 50 3/4 30 3/16 24 3/16...
  • Page 48 528195-YTG-I-0513 XP078-150 Unit Electrical Entry Disconnect Swith Cover Power Entry Ø 2-1/2 Control Entry Ø 7/8 Power Entry Ø 2-1/2 Convenience Outlet Cover Convenience Outlet Power Entry Ø 7/8 FRONT XP078-120 Unit Side Duct Openings 1 8 - 1 /4 D o t P l u g s R e tu r n A i r...
  • Page 49 528195-YTG-I-0513 XP150 Unit Side Duct Openings Dot Plugs 18-1/4 5-5/32 2-7/8 31-5/8 Side Duct Dimensions Dimension (in.) Unit Model Number 28 1/4 18 1/16 28 1/4 18 1/4 28 1/4 18 1/16 28 1/4 18 1/4 28 1/4 18 1/16 28 1/4 18 1/4 28 1/4...
  • Page 50 528195-YTG-I-0513 XP078-150 Unit Accessory Dimensions XP078-150 Roof Curb RIGHT 80-5/8 INSULATED DECK UNDER CONDENSER SECTION SUPPLY RETURN 2 TYP. 50-1/2 INSULATED DECK UNDER COMPRESSOR SECTION FRONT 8 or 14 XP078-150 Transition Roof Curb 2 TYP 23 4 30-1/2 50-1/2 80-5/8 RETURN SUPPLY 76-5/8...
  • Page 51 528195-YTG-I-0513 XP078-150 Roof Curb Cut Away 2“ 3/4” X 1-1/4” WIDE GASKETING FOR CURB FRAME AND ALL DUCT SUPPORT SURFACES UNIT BASE 3.75” WOOD NAILER 3.56” UNIT BASE RAILS 14” 8“ MIN. ABOVE FINISHED ROOF COUNTERFLASHING CURB FRAME CAN’T STRIP INSULATION AND ROOFING MATERIAL INSULATION ROOF DECK AND SUPPORT STRUCTURE...
  • Page 52: Economizer Options

    528195-YTG-I-0513 Economizer Options Economizer Usage Application Cabinet Height Description Model Bottom Return Downflow economizer with barometric relief 2EE04705924 Side Return Horizontal economizer without barometric relief 2EE04706024 42" Slab Economizer, 42” tall cabinet 2EE04705824 ERV or End Return 50" Slab Economizer, 50” tall cabinet 2EE04705724 1.
  • Page 53 528195-YTG-I-0513 Field Installed Horizontal Economizer W/Power Exhaust 2EE04706024 Return Air Damper Field Installed Duct Work 2EE04706024 Fresh Air Damper 2PE047032XX Power Exhaust 1EH0408 1EH0408 2EE04706024 Barometric Barometric Fresh Air Hood Relief Damper Relief Hood Slab Economizer Downflow W/Power Exhaust 1EH0409 Fresh Air Hood 2EE04705X24 2PE047032XX...
  • Page 54 Barometric Relief Hood 2PE047032XX 1EH0409 Power Exhaust Barometric Relief Damper Subject to change without notice. Printed in U.S.A. 528195-YTG-I-0513 Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: 528195-YTG-H-0213 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069...