Specifications - Toshiba G9000 Series Installation And Operation Manual

Scib energy storage system
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

Discharging the Batteries
1. The SCiB battery cabinet with provide power to the UPS if the main power of the UPS is lost.
2. The "Discharge" LED is illuminated to indicate the battery cabinet is discharging and the "Ready" LED will be off.
3. The "Discharge" LED will be steady on.
4. As the SCiB battery voltage comes down and gets close the UPS cutoff or shutdown set point, the "Discharge" LED
will start blinking indicating the SCiB is close to the shutdown voltage.
5. Ensure that 'Starting the UPS and Charging the Batteries" procedure is followed when resuming UPS operation after
a discharge ending in UPS cutoff has occurred.
9

Specifications

34
G9000 SCIB ENERGY STORAGE SYSTEM
Capacity
Nominal Voltage
Voltage Range
Maximum Charge Voltage
Maximum System Charge Current
DC Current Max
DC Breaker Rating
Module Type
Operating Temperature
Ambient Humidity
Enclosure
Storage Temperature
Weight
AC Input (Control Power)
Maximum Number of ESS cabinets
that may be paralleled by direct
bus bar connection
Maximum Number of ESS cabinets
in a single UPS System
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002
44.7kWh, 90Ah
497VDC
455-565VDC
565VDC
32ADC
560A
600A
Type 3-23 2P12S Module
0 to 40C
85% RH or Less (No condensation)
NEMA 1, Indoor Only
0 to 40C
1950 lbs
480VAC, 5A, 2PH, 2W
4
8