Bits 8-15: reserved
40011 – Cabinet Fault Status
•
Values: 1 – True, 0 – False
◦
Bit 0: Breaker Open
◦
Bit 1: Fuse Open
◦
Bit 2: Tray Open
◦
Bit 3: Host-Host CAN COM Fault
◦
Bits 4-15: Reserved
40012 – Left String Fault Status
•
Values: 1 – True, 0 – False
◦
Bit 0: Left string over cell temperature fault (protected by BMU)
◦
Bit 1: Left string over cell voltage fault (protected by BMU)
◦
Bit 2: Left string under cell voltage fault (protected- by BMU)
◦
Bit 3: Left string BMU-Host COM fault
◦
Bit 4: Left string BMU hardware failure
◦
Bit 5: Left string close contactor failure
◦
Bits 6-15: Reserved
40013 – Right String Fault Status
•
Values: 1 – True, 0 – False
◦
Bit 0: Left string over cell temperature fault (protected by BMU)
◦
Bit 1: Left string over cell voltage fault (protected by BMU)
◦
Bit 2: Left string under cell voltage fault (protected- by BMU)
◦
Bit 3: Left string BMU-Host COM fault
◦
Bit 4: Left string BMU hardware failure
◦
Bit 5: Left string close contactor failure
◦
Bits 6-15: Reserved
40014 – System Warning Status
•
Values: 1 – True, 0 – False
◦
Bit 0: Left string contactor open
◦
Bit 1: Left string over cell temperature warning
◦
Bit 2: Left string over cell voltage warning
◦
Bit 3: Left string under cell voltage warning
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002