Bits 8-15: reserved
40011 – Cabinet Fault Status
Values: 1 – True, 0 – False
Bit 0: Breaker Open
Bit 1: Fuse Open
Bit 2: Tray Open
Bit 3: Host-Host CAN COM Fault
Bits 4-15: Reserved
40012 – Left String Fault Status
Values: 1 – True, 0 – False
Bit 0: Left string over cell temperature fault (protected by BMU)
Bit 1: Left string over cell voltage fault (protected by BMU)
Bit 2: Left string under cell voltage fault (protected- by BMU)
Bit 3: Left string BMU-Host COM fault
Bit 4: Left string BMU hardware failure
Bit 5: Left string close contactor failure
Bits 6-15: Reserved
40013 – Right String Fault Status
Values: 1 – True, 0 – False
Bit 0: Left string over cell temperature fault (protected by BMU)
Bit 1: Left string over cell voltage fault (protected by BMU)
Bit 2: Left string under cell voltage fault (protected- by BMU)
Bit 3: Left string BMU-Host COM fault
Bit 4: Left string BMU hardware failure
Bit 5: Left string close contactor failure
Bits 6-15: Reserved
40014 – System Warning Status
Values: 1 – True, 0 – False
Bit 0: Left string contactor open
Bit 1: Left string over cell temperature warning
Bit 2: Left string over cell voltage warning
Bit 3: Left string under cell voltage warning
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002
43