Storage/Operating Environment; Inspection/Storage; Storage Environment - Toshiba G9000 Series Installation And Operation Manual

Scib energy storage system
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

6

Storage/Operating Environment

6.1

Inspection/Storage

Inspection
Upon receipt of the SCiB Energy Storage System, an inspection for shipping damage should be performed. Use caution
when removing units from pallets. Refer to labels or documentation attached to packing material.
Unpacking
Check the exterior of units for loose, broken, bent or otherwise damaged parts. Interior inspection should only be performed
by qualified personnel. If damage has occurred during shipping, keep all original crating and packing materials for return to
the shipping agent.
NOTE: The factory warranty does not apply to damage incurred during shipping!
Ensure that the rated capacity and the model number specified on the nameplate conform to the order specifications.
Storage
During periods of non-use, the following guidelines are recommended for storage.
Storage Preparation
1. Power up the G9000 UPS and allow it to operate with no load for at least two (2)* hours to fully charge the SCiB
ESS. (*For a single-cabinet ESS. Additional cabinets will require more time.)
2. Stop the UPS.
3. Place the UPS Main Circuit Breaker switch in the "OFF" position.
4. Place all SCiB ESS Circuit Breaker switches in the "OFF" position.
5. If present, place all MBS Circuit Breaker switches in the "OFF" position.
6.2

Storage Environment

Observe the following when storing the SCiB Energy Storage System.
Store UPS indoors.
Maximum storage time for the SCiB ESS between powered operation cycles is three years. If the ESS has been
stored for a period exceeding 36 months, contact your factory authorized representative for guidance in starting
the unit.
Temperature fluctuations should be minimized.
The optimal storage temperature range is 68 – 77 °F (20 – 25° C).
A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.
The optimal relative humidity at the storage location should be between 50 – 60%.
Humidity must not exceed 90%.
Avoid locations where UPS may be exposed to corrosive gas.
Avoid locations with dirt and/or dust.
14
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002