Technician Settings P52 to P57

P52 – Cool valve proportional band (FC only)
Range: 2...10°C / 4...20°F
Default: 2°C / 4°F
0-10V Valve opening from fully closed to fully open.
P53 – Cool proportional low limit (FC only)
Range: 0...100%
Default: 0%
Minimum valve opening.
P54 – Cool proportional high limit (FC only)
Range: 0...100%
Default: 100%
Maximum valve opening.
P55 – Heat valve proportional band (FC only)
Range: 2...10°C / 4...20°F
Default: 2°C / 4°F
0-10V Valve opening from fully closed to fully open.
P56 – Heat proportional low limit (FC only)
Range: 0...100%
Default: 0%
Minimum valve opening.
P57 – Heat proportional high limit (FC only)
Range: 0...100%
Default: 100%
Maximum valve opening.