Technician Settings P31 to P34

P31 – P34
Fan on/off delay
with fan on demand (auto fan) active.
P31 – Fan ON delay in cooling (FC only)
Range: 0...120 seconds
Default: 0 seconds (no delay)
P32 – Fan OFF delay in cooling
Range: 0...120 seconds
Default: 0 seconds (no delay)
P33 – Fan ON delay in heating (FC only)
Range: 0...120 seconds
Default: 0 seconds (no delay)
P34 – Fan OFF delay in heating
Range: 0...120 seconds
Default: 30 seconds