Technician Settings P47 to P48
P47-48
Heat differential band / offset
(with heat differential band offset = 0)
P47-48
Heat differential band / offset
(with heat differential band offset ≠ 0)
P47 – Heat differential band
Range: 0.5...5°C / 1...10°F
Default: 1°C / 2°F
P48 – Heat differential band offset
Range: -5...+5°C / -9...+9°F
Default: 0°C / 0°F
ComfortVu™ BACnet Thermostat Model Standard TB-HM (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide
52