Carrier PERFORMANCETSERIES EDGER THERMIDISTATT CONTROL TP-NRH-A Installation Instructions Manual

Carrier PERFORMANCETSERIES EDGER THERMIDISTATT CONTROL TP-NRH-A Installation Instructions Manual

Performance series edge thermidistat programmable & non−programmable control

Advertisement

TP-PRH-A, TP-NRH-A
PerformancetSeries
Edger Thermidistatt Control

Installation Instructions

Programmable Control
NOTE: Read the entire instruction manual before starting the installation.
US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1, US6956463 B2.
A07049
Non−Programmable Control
Designed and Assembled
in the USA.
A07048

Advertisement

Table of Contents
loading

Summary of Contents for Carrier PERFORMANCETSERIES EDGER THERMIDISTATT CONTROL TP-NRH-A

  • Page 1: Installation Instructions

    TP-PRH-A, TP-NRH-A PerformancetSeries Edger Thermidistatt Control Installation Instructions Programmable Control NOTE: Read the entire instruction manual before starting the installation. US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1, US6956463 B2. A07049 Designed and Assembled Non−Programmable Control in the USA. A07048...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS SAFETY CONSIDERATIONS INTRODUCTION ..........INSTALLATION CONSIDERATIONS INSTALLATION .
  • Page 3: Introduction

    During power loss its internal memory saves settings for unlimited time, and the clock continues to run for at least 24 hours. An extension of Carrier’s proven line of thermostats; it provides separate setpoints for heating and cooling in addition to humidification and dehumidification.
  • Page 4: Installation Considerations

    INSTALLATION CONSIDERATIONS Power This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low−voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper.
  • Page 5 There are programmable and non−programmable models for all applications. They can be configured for AC or HP, 1−or 2−speed compressor, and for Hybrid Heatt installations, allowing it to be used in place of all Carrier thermostats. Programmable Thermidistat Controls may be configured as non−programmable if user desires.
  • Page 6 ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. DO NOT connect furnace HUM terminal directly to Thermidistat Control HUM terminal. This will bypass furnace safety controls. See Low Voltage Wiring Diagrams and notes for proper connection.
  • Page 7 Remote Indoor Temperature Sensor A remote temperature sensor may be used with the programmable model, where it is desirable to install the Thermidistat Control in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand alone or average with local sensor.
  • Page 8: Installation

    Carton contains the following components. See Fig. 2 for TP−PRH−A or Fig. 3 for TP−NRH−A. Fig. 2 − TP−PRH−A Carton Contents 1. Display Module 2. Stand−off for Equipment Control Module 3. Outside Air Temperature Sensor, screws and pigtail 4. Equipment Control Module INSTALLATION A07685...
  • Page 9 Fig. 3 − TP−NRH−A Carton Contents 1. Display Module 2. Stand−off for Equipment Control Module 3. Outside Air Temperature Sensor, screws and pigtail 4. Equipment Control Module Thermidistat Control Location Thermidistat Control should be mounted: Approximately 5 ft (1.5m) from floor. Close to or in a frequently used room, preferably on an inside partitioning wall.
  • Page 10 Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature−radiating objects which could cause a false reading. Close to or in direct airflow from supply registers and return−air registers. In areas with poor air circulation, such as behind a door or in an alcove.
  • Page 11 UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage Thermidistat Control. Check to make sure wiring is correct before proceeding with installation or turning on power. 1. Turn off all power to equipment. 2.
  • Page 12 ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental damage. Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly. Two−Piece Installation The following steps should be followed for the installation of the two−piece configuration.
  • Page 13 A07225 Fig. 4 − Press Tabs to Remove Backplate A07226 Fig. 5 − Take Apart...
  • Page 14 2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be leveled for proper operation) and mark wall through 4 mounting holes. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors.
  • Page 15 6. Match and connect equipment wires to proper terminals of each connector block, being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base. If wires are connected incorrectly, the Display Module will not operate.
  • Page 16 A07166 Fig. 8 − Secure Wires to Terminal Strip A07167 Fig. 9 − Connect Pigtail Wires to Display Module...
  • Page 17 NOTE: The 2−wire pigtail is not intended to support the weight of the Display Module. Do not hang the Display Module from the Equipment Control Module screw terminals. S Red of the pigtail is V+ S Black of the pigtail is Vg 7.
  • Page 18 10. Find suitable indoor mounting location for Equipment Control Module, either near or on equipment. See Fig. 11. IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or below any other controls or equipment (i.e. humidistat, humidifier, etc.). Fig.
  • Page 19 NOTE: Standoffs are provided as an aid when installing Equipment Control Module on inside equipment or a solid wall. 12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base.
  • Page 20 Fig. 13 − Cover on Equipment Control Module 14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2−digit code appears on large display which identifies Thermidistat Control configuration. Refer to Option 33. a.
  • Page 21 Single−Piece Installation The following steps should be followed for the installation of the single−piece configuration. 1. Remove cover from Equipment Control Module by pressing the two tabs on the bottom edge and pulling away. Route wires through large hole in Equipment Control Module.
  • Page 22 Fig. 14 − Equipment Control Module 5. Match and connect equipment wires to proper terminals of each connector block. 6. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement.
  • Page 23 Fig. 15 − Reattach Display Module 9. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2−digit code appears on large display which identifies Thermidistat Control configuration. Refer to Option 33. a.
  • Page 24 Set Thermidistat Control Configuration Configuration options enable the installer to configure the Thermidistat Control for a particular installation. Most are not presented to the homeowner and therefore must be properly set by the installer. (Only those marked with an asterisk * below are available to the homeowner.) The homeowner configurations are described in the owner’s manual.
  • Page 25 Option 11 — Adjustable Setpoint Deadband (not available on heat only and cool only systems) Option 12 — Smart Recovery (programmable models only) Option 13 — Room Temperature Offset Adjustment Option 14 — Humidity Offset Adjustment Option 15 — Enable Auto Mode Option 16 —...
  • Page 26 Option 31* — Daylight Savings Time Configuration (programmable models only) Option 32 — Furnace Heat Staging Option 33 — Single or Two−Piece Installation Option 34 — Hybrid Heat Furnace Latch Option 40 — Fan Humidify Option 41 — Variable Speed Blower Option 42 —...
  • Page 27 flashing is changed by using the UP/DOWN buttons. All changes made are saved at the time of selection and will be saved in the event of the 3 minute time−out or when installer exits from configuration menu. Configuration Options —Selection Option 01 —...
  • Page 28 Option 03 — Fahrenheit/Centigrade Select between Fahrenheit (F) and Centigrade (C) operation. Factory default is Fahrenheit (F). Option 04 — Fan (G) On With W/W1 This selection determines whether fan (G) output is to be On or OFF when any W/W1 (furnace or strip heat) output is On.
  • Page 29 This selection determines which sensor the control will use for measuring room air temperature. Room air temperature can be sensed in one of three ways; the local sensor (L) located on the Display Module, the remote room air sensor (r), or the average of local and remote sensors (Lr).
  • Page 30 temperature falls below 45_F (7_C), the auxiliary heat will be allowed to turn on and will continue to run until demand is satisfied. Default is OF (off). Option 09 — Heat Pump Lockout Temperature Balance Point (only available when heat pump is used and when outdoor air temperature sensor is present) This selection is only available on Hybrid Heat systems.
  • Page 31 Option 11 — Deadband Setting Between Heat & Cool This option is not available on Heat Only and Cool Only systems. The selection allows the installer to choose how much differential exists between the heating and cooling setpoints. Allowable selections are 1 thru 6. Default is 2.
  • Page 32 Control to automatically change between heating mode and cooling mode when sufficient demand for heating or cooling exists. On — Auto mode is available. OF — Auto mode is not available. Default is On. Option 16 — Maximum Cycles Per Hour This selection limits the number of cycles per hour that the Thermidistat Control allows the system to operate.
  • Page 33 Option 18 — Backlight Configuration When OF (off), the backlight will be lit for 10 seconds after a button is pressed. After 10 seconds of no button presses, the backlight turns off. When On, the backlight will normally be on and dim in appearance. The backlight brightness becomes brighter when a button is pressed.
  • Page 34 cooling equipment when the dry contact is closed. See Wiring Diagrams for more information. Default is OF (off). Option 19 — Dry Contact Configuration (non−programmable models only) OF — The dry contact is always de−energized. ON — The dry contact will operate as a DH relay. This relay is reverse logic. When the humidity level is above the dehumidify setpoint, the dry contact D1−D2 will be opened.
  • Page 35 2 — The user has access to change the setpoints only. 3 — The entire keypad is locked. When a button is pressed, the backlight will turn on but none of the operating parameters will be changed. When the keypad lock selection is turned on, the padlock icon will be displayed. To unlock the keypad, press and hold the UP/DOWN buttons simultaneously for five seconds.
  • Page 36 Option 22 — High Cool Latch Temperature (only available if outdoor sensor is present) An outdoor sensor is required for high cool latch feature. This selection is only available when Option 1 is set to H2, A2, or h2 and when Option 7 (zoning) is set to OF (off).
  • Page 37 20 to 50_F (−7 to 10_C) — Outdoor temperature below which both first and second stages of the compressor are energized to satisfy all heating demands. When a cycle starts under a high heat latch, it will finish the heating cycle on high stage.
  • Page 38 deadband Option 11, such that the minimum of the range is 50_F/10_C plus the adjustable deadband and the maximum is 90_F/32_C. Default is 52_F/11_C (based on the adjustable deadband default = 2). Option 27 — Maximum Heating Setpoint This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value Option 11, such that the minimum of the range is 50_F/10_C and the maximum is 90_F/32_C minus the deadband.
  • Page 39 1−24 — The number of months after which the Humidifier Pad Reminder icon will be displayed, “CHECK HUM PAD”. Default is OF (off). Option 30 — Programmable Fan (programmable models only) This selection allows the homeowner to program the fan selection to “Auto” or “On”...
  • Page 40 be set in the clock hours location (range 1−12) and the week of the month will be set in the clock minutes location. The week of the month selections will be F, 2, 3, 4, and L for First, 2nd, 3rd, 4th, and Last. So for the first Sunday in April, the display would show SUN, 4, F.
  • Page 41 Option 34 − Hybrid Heat Furnace Latch This selection allows a Hybrid Heat system to finish a heating cycle using the furnace. On − Once the furnace is on, it will finish the heating cycle with the furnace. If a heat pump defrost occurs, the heating cycle will finish with the furnace.
  • Page 42 Off − The system has a single speed (PSC) blower. On − The system has a variable speed blower. Factory default is OF (Off) Option 42 — Variable Speed Super Dehumidification This option will only be available if the Variable Speed Blower setup (Option 41) has been set to ON.
  • Page 43 Option 44 — Super Comfort Heat This option is only available on heat pump units HP (HP, H2, hh, and h2) when Option 41 (Variable Speed Blower) is set to On and the system has a valid OAT sensor. OF (Off) − Comfort Heat is off On −...
  • Page 44 Option 99 — Reset to Factory Defaults Use this capability to reset the Thermidistat Control to “out of the box” conditions. BEWARE! All configuration settings, program settings, clock, and calendar which have been manually entered will be lost! When this option is selected, the configuration number (99), will appear on the left and 10 will appear on the right.
  • Page 45: System Start−Up And Checkout

    SYSTEM START−UP AND CHECKOUT The Thermidistat Control is designed with a built−in installer test capability. It allows easy operation of equipment without delays or setpoint adjustments to force heating or cooling. To enable installer test mode, press and hold the fan button for 15 seconds.
  • Page 46 non−programmable models, pressing the features button shall toggle the state of the dry contact. In a heat pump application, when the mode is set to “em heat” the auxiliary heat will turn on for 3 minutes. The clock display will count down from 180 to 0 during this test.
  • Page 47 If the programmed schedule is to be used, make sure the triangle icon next to the FOLLOW SCHEDULE icon is turned on. Pressing the Schedule button will cycle the triangle icon through the FOLLOW SCHEDULE, HOLD and VACATION selections. If fixed temperatures are desired, use SCHEDULE button to turn on arrow icon next to HOLD.
  • Page 48 When changing Vacation settings, the soft keys are used to choose the selection to be adjusted and the UP/DOWN buttons are used to change the setting. Humidify setting may only be changed when heat mode is selected and Dehumidify setting may only be changed when cool mode is selected. Humidity Control Features The various humidity control features of the Thermidistat Control are explained below.
  • Page 49 2. Auto Humidify Thermidistat Control will automatically adjust the humidity setpoint according to the outdoor temperature. As the outdoor temperature decreases, the humidity setpoint also decreases. Settings ranging from 1 to 9, 1 being the lowest and 9 the highest, will be visible to the homeowner. See Fig.
  • Page 50 Dehumidification Dehumidification is done only during cooling. Depending on type of equipment used, compressor speed, blower speed, setpoint adjustment, and equipment cycling are modified to provide added dehumidification. A dehumidification setpoint (separate from humidification setpoint) is available to the homeowner. It can range from 46% to 66% relative humidity.
  • Page 51 setpoint is adjusted upward by 2% per degree of overcooling. For example, a cooling setpoint of 76_F/24_C and a dehumidify setpoint of 60% is equivalent to a cooling setpoint of 75_F/24_C and a dehumidify setpoint of 62%. This dehumidify setpoint change is internal to the Thermidistat Control and is not shown on the display.
  • Page 52 To Select Dehumidification (programmable − between NORMAL, COOL TO, and OFF) Press the soft key below the dehumidify icon button to bring up dehumidify selections. Dehumidify options are only available when in Cooling mode. When system is in AUTO mode, dehumidify options are available if the last system operation was a call for cooling.
  • Page 53 − output is turned On when no dehumidify demand exists and is turned OFF when demand exists. Carrier FK and FV series variable−speed fan coils, all variable−speed furnaces, and select single and multi−stage furnaces with the dehumidify connection have dehumidify inputs which connect directly to Thermidistat Control dry contact.
  • Page 54 Vacation Setpoints A special set of temperature and humidity setpoints exist which are active in vacation mode. They are adjustable by the homeowner, are exclusively for vacation mode, and are remembered from one vacation selection to the next. See Table 3 for default values. Table 3 –...
  • Page 55: Operational Information

    dehumidify setpoint is accessible by pressing the soft key below the dehumidify icon when the box is around the cooling setpoint. OPERATIONAL INFORMATION Timers Five−Minute Compressor Timeguard This timer prevents compressor from starting unless it has been off for at least 5 minutes.
  • Page 56 Defrost When defrost occurs in a Hybrid Heat system, the furnace will operate during the defrost cycle. At the end of the defrost cycle, the furnace and heat pump will be de−energized while the fan is energized for 2 minutes allowing the heat exchanger to cool down.
  • Page 57 Heat/Cool Setpoints (Desired Temperature) A minimum difference of 1_ and maximum of 6_ is enforced between heating and cooling desired temperatures. This is done by allowing 1 setting to “push” the other, to maintain this difference. This difference is adjustable via Configuration Option 11.
  • Page 58 Programmable Fan (programmable models only) The fan output can be programmed based on period of the day. When programming for each day and period the fan can be set to On or AUTO. If the fan button is pressed to change from On to Auto or vice versa when programmable fan has been enabled, the manual change will only remain in effect until the next program period, when the programmable fan setting will be changed per the scheduled setting.
  • Page 59 See Wiring Diagrams for more information. Relays This thermostat uses latching relays. When the thermostat loses power, the relays will remain in their last position until power is restored and all relays are reset to their correct position. Out of the box, the outputs may appear to be On when the thermostat is not powered.
  • Page 60: Troubleshooting

    TROUBLESHOOTING If the display module doesn’t power up after power is applied, check the Rc/Rh and C terminals for 24VAC. If 24VAC is present, check the voltage between Vg and V+. This voltage will be approximately 12−20VDC. If voltage is present, check the polarity to make sure it is wired correctly.
  • Page 61 E5 − If Thermidistat Control cannot properly read humidity, E5 will be displayed. Replace Thermidistat Control. If both Humidify and Dehumidify have been set to OF, the humidity value will be shown as “−−” when viewed from the humidity menu, but no E5 will be shown in the display. Table 4 can be used as a troubleshooting tool for determining which outputs will be active for a particular configuration and each operating mode.
  • Page 62 Table 4 – Equipment Configuration Outputs EQUIP HARDWARE COOL CONFIG CONFIG STG 1 OPTION 01 SS AC Y/Y2 SS AC Y/Y2 SS HP Y/Y2, RVS + O O/W2/B SS HP Y/Y2 RVS + B SS HP Y/Y2, RVS + O O/W2/B Opt43 = On SS HP...
  • Page 63 Table 4 − Equipment Configuration Outputs (cont.) EQUIP HARDWARE COOL CONFIG CONFIG STG 1 OPTION 01 2SPD HP Y1/W2 RVS + B SS Hybrid Y/Y2, Heat O/W2/B RVS + O SS Hybrid Heat Y/Y2 RVS + B 2S Hybrid Y1/W2 Heat O/W2/B RVS + O...
  • Page 64: Wiring Diagrams

    WIRING DIAGRAMS Display module Display module wall mount * Indicates connection may not be required/available. Fig. 18 − Display to Equipment Control Module Connection Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Y/Y2 Y1 / W2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1...
  • Page 65 Equipment Control Module RVS Cooling O/B W2 Heat Stage 3 W/W1 Heat/Cool Stage 1 Y1 / W2 Heat/Cool Stage 2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN * Indicates connection may not be required/available.
  • Page 66 Equipment Control Module RVS Cooling O/B W2 Heat Stage 2 Heat Stage 3 Y1 / W2 Heat/Cool Stage 1 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available.
  • Page 67 Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN * Indicates connection may not be required/available.
  • Page 68 Equipment Control Module Heat Stage 2 O/B W2 Heat Stage 1 Cool Stage 1 Y1 / W2 Cool Stage 2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available.
  • Page 69 Equipment Control Module Heat Stage 2 Heat Stage 1 Y1 / W2 Cool Stage 1 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available. Fig.
  • Page 70 Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN * Indicates connection may not be required/available.
  • Page 71 Equipment Control Module RVS Cooling O/B W2 Heat Stage 2 Heat Stage 3 Y1 / W2 Heat/Cool Stage 1 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available.
  • Page 72 Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN * Indicates connection may not be required/available.
  • Page 73 Equipment Control Module RVS/Heat Stage 2 Heat Stage 1 Compressor Low Compressor High 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com Fig. 27 − Thermidistat Control w/Dry Contact Control for Fan Run Time O/B W2 W/W1 Y1 / W2...
  • Page 74 Equipment Control Module Heat Stage 2 O/B W2 Heat Stage 1 Y1 / W2 Heat/Cool Stage 1 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available.
  • Page 75 Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 Compressor Low Y1 / W2 Compressor High 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available.
  • Page 76 Equipment Control Module RVS Cooling O/B W2 Heat Stage 3 (furnace) Heat/Cool Stage 1 Y1 / W2 Heat/Cool Stage 2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available.
  • Page 77 Equipment Control Module RVS Cooling O/B W2 Heat Stage 2 W/W1 (furnace) Heat Stage 2 Y1 / W2 Heat/Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN...
  • Page 78 Equipment Control Module Heat Stage 2 O/B W2 Heat Stage 1 Cool Stage 1 Y1 / W2 Cool Stage 2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available.
  • Page 79 Equipment Control Module O/B W2 Heat Stage 1 W/W1 Y1 / W2 Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN * Indicates connection may not be required/available.
  • Page 80 Equipment Control Module RVS Cooling Heat Stage 3 (furnace) Heat Stage 2 (furnace) Heat/Cool Stage 1 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available. ** Some heat pumps may designate W1.
  • Page 81 Equipment Control Module O/B W2 Heat Stage 1 W/W1 Y1 / W2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN * Indicates connection may not be required/available. Fig.
  • Page 82 Equipment Control Module Heat Stage 2 Heat Stage 1 Cool Stage 1 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com * Indicates connection may not be required/available. ** Option 19 set to 2.
  • Page 83 Equipment Control Module Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Y1 / W2 Cool Stage 1 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN * Indicates connection may not be required/available.
  • Page 84: Thermidistat Control Configuration Record

    THERMIDISTAT CONTROL CONFIGURATION Installer _________________________ A. Hardware Configuration __________ Seal Hole In Wall B. Mode Settings __________ Mode (Off, Heat, Cool, Auto, Em Heat) __________ Heating Setpoint Value __________ Cooling Setpoint Value __________ Fan (Auto or On) C. Home, Away, Sleep Settings Heat Cool Home...
  • Page 85 E Configuration Options Option 01 Equipment Type _____ Option 02 Clean Filter Timer Adjustment _____ Option 03* Fahrenheit/Centigrade Selection _____ Option 04 Fan (G) on with W/W1 Selection _____ Option 05 Room Air Temperature Sensing (programmable models only) _____ Option 06 Cooling Lockout Below 55_F/13_C Selection (only available if outdoor air sensor is present) _____ Option 07...
  • Page 86 E Configuration Options (cont) Option 19 Dry Contact (programmable models only) _____ Option 20 Outdoor Air Temperature Offset Adjustment _____ Option 21* Keypad Lockout _____ Option 22 High Cool Latch Temperature _____ Option 23 High Heat Latch Temperature _____ Option 24* Programmable/Non-Programmable (programmable models only) _____ Option 25*...
  • Page 87 E Configuration Options (cont) Option 40 Fan Humidity _____ Option 41 Variable Speed Blower _____ Option 42 Variable Speed Super Dehumidification _____ Option 43 Intelligent Heat Staging _____ Option 44 Super Comfort Heat _____ Option 99 Reset to Factory Defaults _____ * Options with an asterisk can also be set/changed by the homeowner.
  • Page 88 TP-PRH-4SI Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 04/09 Catalog No: TP-PRH-4SI Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Table of Contents