Checks With Voltage Connected To Drive Section; On-Load Checks - ABB ACA 6 Series Hardware Manual

Frequency converters 3 to 4300 kw
Table of Contents

Advertisement

Checks with Voltage
Connected to Drive
Section
1.
Basic Checks
Check that the Prevention of Unexpected Start (if available)
is working.
1. Stop the drive by a Stop command and wait until the
drive has stopped.
2. Open the Prevention of Unexpected Start switch by
closing the switch on the control desk: the circuit will
open. The lamp (if fitted) on the desk should be lit.
3. Give a Start command. The drive should not start.
4. Reset the drive.

On-load Checks

Check the rotation direction of the motor.
Check the pulse encoder functioning (if used)
Check the emergency stop function of the system from each
operating place.
ACS 600 MultiDrive
Basic checks for the Drive Section when voltage is connected to the
Supply Section and DC busbars.
Action
The table below is a commissioning checklist for the loaded Drive
Section.
Action
Chapter 5 – Commissioning the Drive Section
Information
See the circuit diagrams
delivered with the device.
Information
See Pulse Encoder Interface
Module NTAC-02 Installation and
Start-up Manual (EN code
58919730) or NIOB-01 User's
Guide (EN code 64471341).
5-7