Cable Conduit in the
Floor below the Cabinet
With heavy
cabinets support
the structural C-
sections from
below.
ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
A cable conduit can be constructed below the 400 mm wide middle part
of the cabinet. The cabinet weight lies on the two 100 mm wide
transverse sections which the floor must carry.
Viewed from above
Prevent the cooling air flow
from the cable conduit to
the cabinet by bottom
plates. To ensure the
degree of protection for the
cabinet use the original
bottom plates delivered with
the unit. With user-defined
cable entries take care of
the degree of protection and
fire protection.
Chapter 2 – Mechanical Installation
This area can be used for a
cable conduit
Side view
Cables
2-9