ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
The Control Panel is connected to modular jack X19 on NAMC-11/51
board. The modular jacks on NIOC board are not intended for Panel
use (they are used by Standard Modbus Link).
CH2
CH1
V16
V15
Connect the Control Panel cable to terminal X19 of the NAMC-11/51,
or with NAMC-03 board to terminal X28 of the NIOC board.
Earth the cable
screen at the near
earthing screw.
See NIOB-01 User's Guide (EN code 64471341) or Pulse Encoder
Interface Module NTAC-0x Installation and Start-up Guide (EN code
58919730) for the pulse encoder insulation reguirements and
connections.
The pulse encoder shall be insulated from the motor stator or rotor in
order to prevent currents from finding their way out from the drive shaft
through the encoder with resulting damage to the bearings in both the
motor and the encoder.
CH0
INT
BRC
X1
V12
V11
NAMC-11/51 board
NAMC-11/51 with NDCO
X19