Fault' Connector Strip - Siemens FN2012-A1 Mounting & Installation

Ethernet-switch (modular)
Hide thumbs Also See for FN2012-A1:
Table of Contents

Advertisement

Pin assignments
6

'FAULT' connector strip

6.2 'FAULT' connector strip
26 | 34
Building Technologies
Siemens Industry, Inc.
The fault output is a dry contact relay and, depending on the configuration, it can be
used to report fault states by means of contact interruption. When the FN2012 is
switched off, the relay contact is deactivated (opened).
The following fault messages can be configured via the web interface:
'Fatal fault': Ethernet switch (modular) malfunction
'Ring fault': Ring faults are only displayed if the Ethernet switch (modular) has the
function of the 'redundancy manager'
'Ring port fault': 'Link down' state of a ring port
Pin
Designation
F1
OUT
F2
OUT
F3
IN
F4
IN
Admissible cable cross-section: AWG 24...AWG 12 / 0.2...2.5 mm²
F4 F3 F2 F1
IN
OUT
Connector
Terminal Plug
Cover cap
(open)
Description
Dry contact relay 1 (common, normally open)
Dry contact relay 2 (common, normally open)
Not connected
Not connected
F1
F2
F3
F4
A6V10407862_d_en_--
2018-09-07