Siemens FN2012-A1 Mounting & Installation page 22

Ethernet-switch (modular)
Hide thumbs Also See for FN2012-A1:
Table of Contents

Advertisement

Wiring
4
Ethernet switch as a repeater
22 | 34
Building Technologies
Siemens Industry, Inc.
Two repeaters
Ground fault
PoE
Switch1
100 m
P1
P0
P0
P1
P2
P3
P4
P5
MoNet
MoNet
Ethernet
PMI & Mainboard
Panel
Figure 15: 2x Ethernet switch (modular) as a repeater in the electric Ethernet
Jumper settings on the VN2001 with two repeaters:
Switch/repeater
Switch 1
Repeater 1
Repeater 2
Switch 2
Guidelines
Max. two repeaters between two nodes.
Electric Ethernet distance between two nodes maximum 300 ft/100 m.
Repeater power supply via 'Power over Ethernet' (PoE) from the VN2001.
For each switch (node), 1 repeater can be supplied with power.
The switch carries out ground fault supervision as far as the repeater.
If there are two repeaters, the first one transfers ground fault supervision to the
second repeater.
Electrical Ethernet
100 m
P1
P0
P0
P1
P2
P3
P4
P5
MoNet
MoNet
Repeater2
Repeater1
VN2001 in port P1
Not connected
PoE
Neutral position
PoE
PoE & Ground fault
100 m
P1
P1
P0
P0
P1
P2
P3
P4
P5
MoNet
MoNet
PMI & Mainboard
Panel
VN2001 in port P0
PoE
Ground fault supervision
PoE
Not connected
A6V10407862_d_en_--
Switch2
P0
P0
P1
P2
P3
P4
P5
Ethernet
2018-09-07

Advertisement

Table of Contents
loading

Table of Contents