Wiring
4
Ethernet switch as a repeater
22 | 34
Building Technologies
Siemens Industry, Inc.
Two repeaters
Ground fault
PoE
Switch1
100 m
P1
P0
P0
P1
P2
P3
P4
P5
MoNet
MoNet
Ethernet
PMI & Mainboard
Panel
Figure 15: 2x Ethernet switch (modular) as a repeater in the electric Ethernet
Jumper settings on the VN2001 with two repeaters:
Switch/repeater
Switch 1
Repeater 1
Repeater 2
Switch 2
Guidelines
●
Max. two repeaters between two nodes.
●
Electric Ethernet distance between two nodes maximum 300 ft/100 m.
●
Repeater power supply via 'Power over Ethernet' (PoE) from the VN2001.
●
For each switch (node), 1 repeater can be supplied with power.
●
The switch carries out ground fault supervision as far as the repeater.
●
If there are two repeaters, the first one transfers ground fault supervision to the
second repeater.
Electrical Ethernet
100 m
P1
P0
P0
P1
P2
P3
P4
P5
MoNet
MoNet
Repeater2
Repeater1
VN2001 in port P1
Not connected
PoE
Neutral position
PoE
PoE & Ground fault
100 m
P1
P1
P0
P0
P1
P2
P3
P4
P5
MoNet
MoNet
PMI & Mainboard
Panel
VN2001 in port P0
PoE
Ground fault supervision
PoE
Not connected
A6V10407862_d_en_--
Switch2
P0
P0
P1
P2
P3
P4
P5
Ethernet
2018-09-07