Fitting The Top Panels; Mounting The Burner - Viessmann VITOROND 200 Installation Instructions Manual

Type vd2, 320 to 1080 kw oil/gas boiler
Hide thumbs Also See for VITOROND 200:
Table of Contents

Advertisement

Fitting the top panels

A
1.
Fig. 25
Top panel, centre (from 500 kW)
A
Boiler type plate
B

Mounting the burner

Danger
Fibre dust can be produced if working with high
temperature insulation materials that contain zir-
conium or aluminium silicate ceramic fibres. This
fibre dust can be harmful to health.
Only trained personnel may adjust or replace
the insulation. Wear suitable protective clothing,
especially breathing equipment and safety gog-
gles.
Mounting and adjusting the burner:
Burner instructions
If the burner connection was not prepared at the fac-
tory, make the flame tube aperture and the fixing holes
on the supplied blank plate on site.
B 3.9 x 9.5
B 3.9 x 9.5
2.
3.
B
4.
B 3.9 x 9.5
Max. flame tube aperture Ø 360 mm.
Cut out the thermal insulation mat in the boiler door
to suit the blast tube diameter.
After mounting the burner, seal the annular gap
between the flame tube and the thermal insulation
block with the flame tube gasket supplied.
Fig. 26
27