Installation sequence
Electrical connections, heat pump controller
Immersion heater EHE 400 V~
224.7
B
X2.N
A
Fig. 29
Immersion heater EHE, power supply 3/N/PE
A
400 V/50 Hz
Terminals of the heat pump control unit
B
Plug
sXG
Terminals
Function
225.1
Heating circuit pump of the heating
circuit with mixer M2/HC2
M2
r
225.2
Mixer motor control, heating circuit
M2/HC2
M2
Signal mixer CLOSE
225.3
Mixer motor control, heating circuit
M2/HC2
M2
Signal mixer OPEN

Cross connect PCB (signal and safety connections)

Set the required parameters during commissioning:
See page 55 onwards.
34
N
L1
L2
L3
?
(cont.)
Immersion heater 230 V~ (on site)
224.7
B
X2.N
A
Fig. 30
Immersion heater, power supply 1/N/PE
A
230 V/50 Hz
Terminals of the heat pump control unit
B
Explanation
Connect a temperature limiter to restrict the maximum
temperature for underfloor heating circuits (if installed)
in series.
Connection values:
Output: 100 W
Voltage: 230 V~
Max. control current: 4(2) A
Connection values:
Output: 10 W
Voltage: 230 V~
Max. control current: 0.2(0.1) A
Connection values:
Output: 10 W
Voltage: 230 V~
Max. control current: 0.2(0.1) A
N
N N
L1
L1
L1
?