Lennox FLEXY II Series Installation, Operating And Maintenance page 53

Table of Contents

Advertisement

HEATING : GAS BURNER 60 & 120kW
Low Heat Injection Pressure Checks
- Switch the control to Low Heat
- Check and adjust if necessary the Outlet pressure to 3.7
mbar (G20) or 5.1 mbar f or Groningue(G25) & 15.3 mbar
f or propane (G31)(fig.18)
IOM – FLEXY II – 1007 – E
- Af ter the adjustment of the low heat, re-v erify the high
heat
- re-position the stoppers and close the pressure ports.
Pressure adjustments table for each ty pe of gas (mbar)
Category
G20
G25 (Groningue) 25.0 +/- 1.3 5.1 +/- 0.1
G31 (GPL)
Fig.18
Supply
Low Heat
pressure
Injection min.
20.0 +/- 1
3.7 +/- 0.1
37.0 +/- 1.9 15.3 +/- 0.3
High Heat
Injection
10.4+/- 0.2
13.1 +/- 0.2
34.3 +/- 0.6
Page 51